BUSSMANN Effective May 2016 Technical Data 1034 Supersedes December 1998 SERIES Edison base plug fuses dual-element, time-delay, 125 volts, up to 30 amps Recommended fuse holders Catalog Type Catalog Type numbers box numbers box SOU SOY 2 1/4 SRU SRY handy SSU SSY 4 SOW SSY-RL square 2 3/4 SRW STY handy Catalog symbol: SSW SCY SOX SOY-B T - (amps) 4 Single octagon SRX SSN BP/T - (amps) gang Description: Package quantity and weight Bussmann series dual-element, time-delay Edison style plug fuse. Quantity Weight Amp Per Per Per Per 5 ratings box card box cards Specifications: 3/10 to 14 A 4 1 0.210 0.46 Ratings 15 to 30 A 4 3 0.25 1.07 Volts 125 Vac or less Features: Amps 3/10 to 30 A Heavy duty time-delay plug fuse Interrupting rating 10 kA RMS Sym Use to protect critical motor circuits or Agency Information motors that cycle on/off frequently UL Listed (up to 6-1/4 A), Std. 248-11, Guide An industrial/commerical grade product with JFHR, File E56412, (7 to 30 A) Guide JEFV, exclusive dualelement construction File E12112 Edison base size CSA Certified, Class 1423-01, File 53787 These fuses thread into fuse receptacles and CE box cover units Industrial strength, featuring an exclusive Catalog numbers (amps) dual-element construction T - 3/10 T - 2-1/4 T - 7 This spring loaded design provides superior T - 4/10 T - 2-1/2 T - 8 short circuit and overload protection T - 1/2 T - 2-8/10 T - 9 More time-delay than the medium duty Type T - 6/10 T - 3 T - 10 TL fuses in order to better protect industrial motors and critical residential circuits T - 8/10 T - 3-2/10 T - 12 T - 1 T - 3-1/2 T - 14 T - 1-1/8 T - 4 T - 15 T - 1-1/4 T - 4-1/2 T - 20 T - 1-4/10 T - 5 T - 25 T - 1-6/10 T - 5-6/10 T - 30 T - 1-8/10 T - 6 T - 2 T - 6-1/4 Technical Dat a 1034 Edison base plug fuses Effective May 2016 dual-element, time-delay, 125 volts, up to 30 amps Time-current curve average melt Amp rating 100 10 1 0.1 0.01 Current in amps The only controlled copy of this Data Sheet is the electronic read-only version located on the Eaton Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction ofany products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton 1000 Eaton Boulevard For Eatons Bussmann series Cleveland, OH 44122 product information, United States Eaton.com call 1-855-287-7626 or visit: Eaton.com/bussmannseries Bussmann Division Eaton and Bussmann are valuable 114 Old State Road Ellisville, MO 63021 trademarks of Eaton in the US and other United States countries. You are not permitted to use the Eaton.com/bussmannseries Eaton trademarks without prior written consent of Eaton. Follow us on social media to get the 2016 Eaton latest product and support information. All Rights Reserved CSA is a registered trademark of the Printed in USA Canadian Standards Group. Publication No. 1034 SB98107 UL is a registered trademark of the May 2016 Underwriters Laboratories, Inc. Time in seconds 4 10 15 20 30 100 1000 2000