Data Sheet GE CCR0512FP Power Supply 90 - 264V Input 12V , 500W Output ac dc Features Conduction cooling for fan less operation Compact 0.5U Profile Overall Dimensions: Shelf Mount Version: 0.877 in. x 3.35 in. x 8.790 in. Stand Alone Version: 0.888 in. x 4.392 in. x 10.40 in. 12V , 500W Output dc 10.8 to 13.2V Output Voltage Programmability dc Universal AC input with Active PFC Hot Pluggable (Shelf Mount Version) Redundant Parallel Operation Shelf Mount Version Active Load Sharing (Single Wire) Analog, IC or PMBus means of control and monitoring Remote On/Off Remote Sense (up to 0.25V of total compensation) No Minimum Load Requirements Three visual LED Indicators Input, Output and Fault status 3.3V 2A Standby Output dc UL and cUL approved to UL/CSA 62368-1, TUV (EN62368-1), CE Mark (for LVD) and CB Report available ** ISO 9001 and ISO 14001 certified manufacturing facility Compliant to RoHS Directive 2011/65/EU and amended Stand Alone Version Directive (EU) 2015/863. Compliant to REACH Directive (EC) No 1907/2006 Applications Test Equipment Network Support Equipment Storage Area Networks (SAN) Network Attached Storage (NAS) Servers Description The CCR0512FP power supply is a universal ac input, 12V , 500W output fan-less conduction cooled, 0.5U thick product designed for dc environments, where conduction or system airflow is available for cooling. The 0.5U form factor makes locating the supply very flexible and space efficient. The supply includes capability for hot plug and redundant load sharing applications. Standard features 2 include remote sense, output voltage programmability, active load sharing, status LEDs, 3.3V standby output, and analog, I C and dc PMBus control and communication interfaces. PMBus name and logo are registered trademarks of SMIF, Inc. * UL is a registered trademark of Underwriters Laboratories, Inc. CSA is a registered trademark of Canadian Standards Association. VDE is a trademark of Verband Deutscher Elektrotechniker e.V This product is intended for integration into end-user equipment. All of the required procedures of end-use equipment should be followed. ** ISO is a registered trademark of the International Organization of Standards July 28, 2021 2012 General Electric Company. All rights reserved. Page 1 Data Sheet GE CCR0512FP Power Supply 90 - 264V Input 12V , 500W Output ac dc Absolute Maximum Ratings Stresses in excess of the absolute maximum ratings can cause permanent damage. These conditions are absolute stress ratings only. Functional operation of the device is not implied at these or any other conditions in excess of those given in the data sheets specifications sections. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability. Parameter Min Max Unit Input Voltage - Continuous 90 264 V ac o Operating Ambient Temperature (see Thermal Considerations section) -20* 55 C o Operating Case Temperature (Cold Plate) -20* 85 C (*See exceptions for spec variations between -10C to -20C) o Storage Temperature -40 90 C Humidity (non-condensing) 30 95 % Altitude 2250 m Isolation Voltage Input to Output 3000 V ac Input to Chassis 1500 V dc Output and Signal/Comm pin to Chassis 100 V dc Electrical Specifications Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. Parameter Input Min Typ Max Unit Operating Voltage 90 115/230 264 V ac Source Frequency 47 50/60 63 Hz Turn On Voltage (*Turn On Max may increase to 95 V at -20C) 78 85 90* V ac ac Turn Off Voltage (*Turn Off Max may increase to 90 V at -20C) 73 80 85* V ac ac Turn On/Turn Off Hysteresis 3 4 V ac Current, V = 90V 6.8 A IN ac RMS Fuse Rating, 250V 15 A ac Power Factor, 230V , 100% Load 0.96 % ac Inrush Transient Current, V = 264V , T = 25C 50 A IN ac A PEAK Efficiency: V = 115V , 20% load 87.0 % IN ac 50% load 90.0 % 100% load 89.0 % V = 230V , 20% load 87.8 % IN ac 50% load 91.8 % 100% load 91.4 % Holdup Time, V = 90V to 264V 80% load, C = 2,200 F, V 10.8V 12 ms IN ac ac OUT OUT dc Leakage Current to earth ground, V = 264V 3.5 mA IN ac Output 1 Main Output Min Typ Max Unit Voltage Set-point (50% load) 11.98 12.00 12.02 V dc Voltage Programming Limits 10.8 13.2 V dc Voltage Tolerance (due to set point, temperature, load, and line regulation) -2 2 %VOUT, set Load Regulation -100 100 mV dc Line Regulation -40 +40 mV dc Ripple and Noise (C = 0.1F ceramic with 10F tantalum capacitor) OUT Peak-to-peak (20MHz Bandwidth) 120 mV p-p Dynamic Load Response (50% to 100% load transient, 1A/s slew rate) Voltage deviation 5 %V OUT, set Settling Time 1.5 ms Current Range 0 42 A dc Current Limit Inception 110 135 %I O,max Current Sharing Accuracy, >20% load -5 5 %I O,max External Capacitance Range 0 10,000 F Turn On Delay Time from AC Input (*Delay Time Max may increase to 3s at -20C) 2* s Turn On Delay Time from Remote On, V within limits 40 ms IN Rise Time (from 10% to 90% of final value) 50 ms Voltage Overshoot 5 %V OUT, set Turn Off Delay Time from Remote On, V within limits 40 ms IN July 28, 2021 2012 General Electric Company. All rights reserved. Page 2