Data Sheet GE Energy CP2725AC54TE Compact Power Line High Efficiency Rectifier Input: 100-120/200-277 Vac Default Outputs: 54 Vdc 2725W 5 Vdc 4W Features Efficiency 96.2% 3 Compact 1RU form factor with 30 W/in density Constant power from 52 58Vdc 2725W from nominal 200 277Vac 1200W from nominal 100 120Vac Output voltage programmable from 42V 58Vdc 2 PMBus compliant dual I C and RS485 serial busses Power factor correction (meets EN/IEC 61000-3-2 and EN 60555-2 requirements) Output overvoltage and overload protection AC Input overvoltage and undervoltage protection Over-temperature warning and protection Applications Redundant, parallel operation with active load sharing Redundant +5V Aux power 48Vdc distributed power architectures Remote ON/OFF Routers/Switches Internally controlled Variable-speed fan VoIP/Soft Switches Hot insertion/removal (hot plug) LAN/WAN/MAN applications Four front panel LED indicators File servers UL* Recognized to UL60950-1, CAN/ CSA C22.2 No. Indoor wireless 60950-1, and VDE 0805-1 Licensed to IEC60950-1 Telecommunications equipment CE mark meets 2006/95/EC directive Enterprise Networks RoHS 6 compliant SAN/NAS/iSCSI applications Description The CP2725AC54TE Rectifier provides significant efficiency improvements in the Compact Power Line platform of Rectifiers. High-density front-to-back airflow is designed for minimal space utilization and is highly expandable for future 2 growth. The standard product is provided with both RS485 and dual-redundant I C communications busses that allow it to be used in a broad range of applications. Feature set flexibility makes this rectifier an excellent choice for applications requiring modular ac-to-dc 48Vdc intermediate voltages, such as in distributed power. * UL is a registered trademark of Underwriters Laboratories, Inc. CSA is a registered trademark of Canadian Standards Association. VDE is a trademark of Verband Deutscher Elektrotechniker e.V. This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user equipment should be followed. (The CE mark is placed on selected products.) ** ISO is a registered trademark of the International Organization of Standards. November 26, 2012 2012 General Electric Company. All rights reserved. Data Sheet GE Energy CP2725AC54TE CPL High Efficiency Rectifier Input: 100-120/200-277 Vac Default Output: 54 Vdc 2725W 5 Vdc 4W Electrical Specifications Input Parameter Min Typ Max Units Notes Startup Input Voltage Low-line Operation 90 High-line Operation 185 Operating Voltage Range Low-line Configuration 90 100, 110, 120 140 High-line Configuration 185 200 277 300 Vac Input Voltage Swell (no damage) 305 Input Frequency 47 66 Hz 11.9 At 110 Vac Input Current A 13.1 At 240 Vac Measured at 25C for all line conditions does not Inrush Transient 25 Apk 30 include X-Capacitors charging. Input Leakage Current 2.5 3.5 mA Measured at 265Vac, 60Hz Power Factor 0.96 0.98 From 50% to 100% load. With ORing function, aux. 5V output, dual/redundant 1 Efficiency 30 80% of FL 94.5 96.2 % 2 I C and RS485 communications and POE isolation 20 Measurement starts at zero crossing of the ac voltage, Holdup Time ms and voltage decayed to 40V. 30 For loads below 1200W. Tested at nominal 115V and 230V. Complies to Ride thru 1/2 1 cycle CISPR24 standards Alarm issued via PFW signal going LO 5 ms prior to the 2 Power Fail Warning 3 5 ms main output decaying below 40Vdc. Main Output Parameter Min Typ Max Units Notes Output Power 1200 At low-line input from nominal 100-120Vac. 2725 W At high-line input from nominal 200-277Vac 2000 At nominal 277Vac and Tamb > 45C Default Set point 54 Vdc Output floats with respect to frame ground. -1 +1 0 45C, minimum load 2.5A 3 Overall Regulation % -2 +2 > 45C Output Voltage Set Range 44 58 Vdc Analog margining. 2 42 58 Vdc Set either by I C, RS485 Output current 1 25 At 1200W, 54V 100-120Vac. 1 50.5/52.4 At 2725W, 54V/52V 200-240Vac. A 1 37/38.4 At 2000W, 54V/52V 277Vac and T > 45C. amb 1 At 240Vrms and 25C. See efficiency curves at the end of this document. 2 Internal protection circuits may override the PFW signal and may trigger an immediate shutdown. 3 Includes all variations due to specified load range, drift, and environmental conditions. November 26, 2012 2012 General Electric Company. All rights reserved. Page 2