Data sheet GE CP3000AC54TE-F Compact Power Line High Efficiency Rectifier 100-120/200-264V input Default Outputs: 54V 3000W, 5V 3.75W AC DC DC Features RoHS Compliant Efficiency 95.6% 3 Compact 1RU form factor with 28 W/in density Constant power from 52 58VDC 3000W from nominal 200 264VAC 1400W from nominal 100 120V AC Output voltage programmable from 42V 58VDC 2 PMBus compliant dual I C serial busses 2 Isolated +5V Aux, signals and I C communications Power factor correction (meets EN/IEC 61000-3-2 and EN 60555-2 requirements) Applications Output overvoltage and overload protection AC Input overvoltage and undervoltage protection 48VDC distributed power architectures Over-temperature warning and protection Routers/Switches Redundant, parallel operation with active load sharing VoIP/Soft Switches Remote ON/OFF LAN/WAN/MAN applications Internally controlled Variable-speed fan File servers Hot insertion/removal (hot plug) Indoor wireless Two front panel LED indicators Telecommunications equipment UL* Recognized to UL60950-1, CAN/ CSA C22.2 No. Enterprise Networks 60950-1, and VDE 0805-1 Licensed to IEC60950-1 SAN/NAS/iSCSI applications CE mark meets 2006/95/EC directive RoHS 6 compliant Description The CP3000AC54TE-F Rectifier provides significant efficiency improvements in the Compact Power Line platform of Rectifiers. High- density front-to-back airflow is designed for minimal space utilization and is highly expandable for future growth. The wide-input 2 standard product is designed to be deployed internationally. It is configured with dual-redundant I C communications busses that allow it to be used in a broad range of applications. These signals and the 5V auxiliary supply are isolated from the main output and frame ground. Feature set flexibility makes this rectifier an excellent choice for applications requiring modular AC to - 48V DC intermediate voltages, such as in distributed power. * UL is a registered trademark of Underwriters Laboratories, Inc. CSA is a registered trademark of Canadian Standards Association. VDE is a trademark of Verband Deutscher Elektrotechniker e.V. This product is intended for integration into end-user equipment. All CE marking procedures of end-user equipment should be followed. (The CE mark is placed on selected products.) ** ISO is a registered trademark of the International Organization of Standards + The PMBus name and logo are registered trademarks of the System Management Interface Forum (SMIF) July 10, 2015 2013 General Electric Company. All rights reserved. Data sheet GE CP3000AC54TE-F CPL High Efficiency Rectifier 100-120/200-264V input Default Outputs: 54V 3000W, 5V 3.75W AC DC DC Absolute Maximum Ratings Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability. Parameter Symbol Min Max Unit Input Voltage: Continuous VIN 0 264 VAC 1 Operating Ambient Temperature TA -10 75 C Storage Temperature Tstg -40 85 C I/O Isolation voltage to Frame (100% factory Hi-Pot tested) 1500 V AC Electrical Specifications Unless otherwise indicated, specifications apply over all operating input voltage, Vo=54V , resistive load, and temperature DC conditions. INPUT Parameter Symbol Min Typ Max Unit Startup Input Voltage Low-line Operation 90 High-line Operation 185 Operating Voltage Range Low-line Configuration 90 100 120 140 V V IN AC High-line Configuration 185 200 - 240 264 Input Voltage Swell (no damage) 264 Input turn OFF 78 80 82 Input turn ON 83 85 87 Input Frequency F 47 66 Hz IN Input protection fuse (314025 or 324025 .MX280 Series (pigtail type) 25 A 18 Input Current at 90V /1200W AC 16.1 at 100VAC/1200W 14 at 110VAC/1200W at 185V /3000W AC IIN 18 AAC at 200V /3000W AC 16.5 at 208VAC/3000W 15.9 at 240VAC/3000W 13.4 11.9 Input Current at 110VAC I A IN AC at 240V AC 13.1 Inrush Transient (at 25C, excluding X-Capacitor charging) I 25 30 A IN PK 8.2 Idle Power (at 220VAC) 54V OFF P W IN 54V ON Io=0 16 Input Leakage Current (264V , 60Hz) I 2.0 mA AC IN Power Factor (50 100% load) PF 0.96 0.995 2 Efficiency (30 80% of FL, 240VAC 25C) 94.5 95.6 % 20 Holdup time (240VAC output may decay from 54 to 40VDC) FL T ms (120V output may decay from 54 to 40V ) FL AC DC 40 Ride thru (tested at 115V 230V. (Complies to CISPR24) T 1/2 1 cycle 3 Power Fail Warning (main output allowed to decay to 40V ) PFW 3 5 ms DC Isolation (per EN60950) (consult factory for testing to this requirement) Input-Chassis/Signals V 1500 V AC Input - Output 3000 VAC 1 Derated above 50C at 2.5%/C 2 See efficiency curve in the Characteristics Curves section. 3 Internal protection circuits may override the PFW signal and may trigger an immediate shutdown. July 10, 2015 2013 General Electric Company. All rights reserved. Page 2