Data Sheet GE GP100H3M54TE Global Platform Line High Efficiency Rectifier 3 -380/480V Input Default Outputs: 54/52V 6000W, 5V 10W AC DC DC Features Efficiency 96.5% typical, exceeds 80plus Titanium levels 3 Compact 1RU form factor with 30 W/in density Constant power from 48 58VDC 6000W from nominal 3-380/480VAC Output voltage programmable from 42V 58VDC 2 PMBus compliant dual, redundant I C serial bus Power factor correction (meets EN/IEC 61000-3-2 and RoHS Compliant EN 60555-2 requirements) Output overvoltage and overload protection Applications AC Input overvoltage and undervoltage protection 48V distributed power architectures DC Over-temperature warning and protection Routers/ VoIP/Soft and other Telecom Switches Redundant, parallel operation with active load sharing LAN/WAN/MAN applications Redundant +5V 2A Aux power File servers, Enterprise Networks, Indoor wireless Remote ON/OFF SAN/NAS/iSCSI applications Internally controlled Variable-speed fan Hot insertion/removal (hot plug) Three front panel LED indicators nd EN/IEC/UL/CSA C22.2 60950-1 2 edition +A1, CCC CE mark Meets FCC part 15, EN55022 Class A standards Meets EN61000 immunity and transient standards Shock & vibration: Meets IPC 9592 Class II standards Description The GP100H3M54TE Rectifier provides significant efficiency improvements in the Global Platform of Power supplies. High-density front-to-back airflow is designed for minimal space utilization and is highly expandable for future growth. The 3 - 380/480Vrms 2 C standard product is designed to be deployed internationally. It is configured with dual-redundant PMBus compliant I communications busses that allow it to be used in a broad range of applications. Feature set flexibility makes this rectifier an excellent choice for applications requiring modular, very-high-efficiency AC to - 48V intermediate voltages, such as in distributed DC power. * UL is a registered trademark of Underwriters Laboratories, Inc. CSA is a registered trademark of Canadian Standards Association. VDE is a trademark of Verband Deutscher Elektrotechniker e.V. This product is intended for integration into end-user equipment. All CE marking procedures of end-user equipment should be followed. (The CE mark is placed on selected products.) ** ISO is a registered trademark of the International Organization of Standards + The PMBus name and logo are registered trademarks of the System Management Interface Forum (SMIF) April 29, 2015 2013 General Electric Company. All rights reserved. Data Sheet GE GP100H3M54TE Global Platform Line High Efficiency Rectifier 3 -380/480V input Default Outputs: 54V 6000W, 5V 10W AC DC DC Absolute Maximum Ratings Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability. Parameter Symbol Min Max Unit Input Voltage: Continuous V 0 600 V IN AC 1 Operating Ambient Temperature T -10 75 C A Storage Temperature T -40 85 C stg I/O Isolation voltage to Frame (100% factory Hi-Pot tested) 2087 V AC Electrical Specifications Unless otherwise indicated, specifications apply over all operating input voltage, Vo=54V , resistive load, and temperature DC conditions. To meet measurement accuracy a warm up time of 1hr may be required. INPUT Parameter Symbol Min Typ Max Unit V 320 380/480 530 Operating Voltage Range (3 delta with safety frame ground) IN Low voltage Turn-OFF (300) 320 VIN Turn-ON (315) 330 V AC Hysteresis 5 High voltage Turn-OFF 530 (550) Turn-ON 5VIN 20 (540) Hysteresis 5 Input voltage phase unbalance VIN -15 10 % Frequency max. slew rate FIN 47 63 Hz Operating Current (3 - all phases operational) IIN 15 AAC Input current phase unbalance load > 50% of FL 1 % Inrush Transient (per at 480VRMS , 25C, excluding X-Capacitor IIN 25 30 APK charging) Source Impedance (NEC allows 2.5% of source voltage drop inside a 0.20 0.25 building) 54V OFF 15 Idle Power (at 480VAC, 25 C) PIN W 54V ON Io=0 25 Leakage Current (per , 530VAC, 60Hz) IIN 2.5 3.5 mA Power Factor (50 100% load) PF 0.96 0.995 Efficiency (380/480V 25C) 10% load 91 AC 20% load 95 % 50% load 97.5 100% load 92 Holdup time (V = 320V , V 42V constant power load) T 10 12 ms in rms out DC, Ride through (at 480VAC, 25 C, constant power load) T 1/2 1 cycle 2 Power Fail Warning (V 42V P = constant power) PFW 5 8 12 ms OUT DC, OUT Isolation (per EN60950) Input Output 3000 V AC V Input-Chassis/Signals 2000 VAC 1 Derated above 50C at 2.5%/C 2 Internal protection circuits may override the PFW signal and may trigger an immediate shutdown. April 29, 2015 2013 General Electric Company. All rights reserved. Page 2