Click on Series name for product info on aimtec.com Series AMEOS40-MAZ 40 Watt AC-DC / DC-DC Converter FEATURES: 4000VAC I/O isolation Energy star compliant Operating temperature: -40C to +85C RoHS compliant Over load, Over voltage, Short circuit protection Low ripple and noise Universal Input: 90-260VAC, 47-440Hz, or 130-370VDC CE, cULus, CB approvals CB Models Single output Input Voltage Input Voltage Output Voltage Output Current Efficiency Model (VAC/Hz) (VDC) (V) max (A) (%) AMEOS40-3.3SMAZ 90-264/47-440 130-370 3.3 8 78 AMEOS40-5SMAZ 90-264/47-440 130-370 5 8 82 AMEOS40-12SMAZ 90-264/47-440 130-370 12 3.33 84 AMEOS40-15SMAZ 90-264/47-440 130-370 15 2.66 83 AMEOS40-24SMAZ 90-264/47-440 130-370 24 1.66 82 Models Dual output Input Voltage Input Voltage Output Voltage Output Current Efficiency Model (VAC/Hz) (VDC) (V) max(A) (%) AMEOS40-5DMAZ 90-264/47-440 130-370 5 4 80 AMEOS40-12DMAZ 90-264/47-440 130-370 12 1.66 85 AMEOS40-15DMAZ 90-264/47-440 130-370 15 1.33 82 AMEOS40-24DMAZ 90-264/47-440 130-370 24 0.835 77 NOTE: All specifications in this datasheet are measured at an ambient temperature of 25C, humidity<75%, nominal input voltage and at rated output load unless otherwise specified. Input Specifications Parameters Conditions Typical Maximum Units 115 VAC 1000 Current mA 230 VAC 530 115 VAC 25 Inrush current <2ms A 230 VAC 50 Leakage current 150 A External fuse Recommended slow blow type 3.15 A Input dissipation No load 0.5 W Start-up time 117 ms Output Specifications Parameters Conditions Typical Maximum Units Voltage accuracy 2 % Line regulation (LL-HL) 0.5 % 0-100% load single 1 Load regulation % 0-100% load dual 2 st nd Cross regulation 25% load - 1 out, 100% load 2 out 5 % Maximum Capacitive load Depending of the model 470-23 000 F Transient response deviation 25% load Step 2 % of Vout Ripple & Noise* 20MHz bandwidth 50 mV p-p Hold-up time (min) 115VAC 29 ms Minimum Load Current 0 % of Max *Ripple & Noise measured with 0.1F M/C and 1F E/C www.aimtec.com Tel: +1 514 620 2722 Toll free: + 1 888 9 AIMTEC (924 6832) F 052e R7.P 1 of 4 North America only Series AMEOS40-MAZ 40 Watt AC-DC / DC-DC Converter Isolation Specifications Parameters Conditions Typical Rated Units Tested I/O voltage 60 sec 4000 VAC Isolation Resistance >1000 M General Specifications Parameters Conditions Typical Maximum Units Switching frequency 47 KHz Protection class Class II Over current protection Auto recovery 110 140 % Over voltage protection Zener diode clamp 110 % Short circuit protection Hiccup mode, indefinite Short Circuit restart Auto recovery o Operating temperature With derating above 55C -40 - +85 C o Maximum case temperature 100 C o Storage temperature -40 to +95 C o Temperature coefficient 0.02 % / C Cooling Free air convection Humidity Non condensing 95 % RH Weight 145 g Dimensions (L X H X W) 4.92 x 2.32 x 1.02 inches 125 x 59 x 26mm, o > 800,000 hrs (MIL-HDBK -217F, t=+25 C)/Full Load MTBF > 200,000 hrs (MIL-HDBK -217F, t=at highest operating temperature)/Full Load Environment Approval Test Parameters Conditions Wave form Half sine wave Acceleration amplitude 5gn Shock Bump duration 30 ms Converter operation Before and after test, body mounted (on chassis) Number of bumps 18 (3 in each direction for every axis) Test mode Sweep sine, 10-100Hz, speed 0.05Hz/s Displacement 1 mm Vibration Acceleration 3g, 3 loops 30min one cycle, 3h total, every axis tested Converter operation Before and after test, body mounted (on chassis) Safety Specifications Parameters Agency approvals cULus, CE, CB Scheme IEC EN UL 60601-1, 2 x MOOP, CSA-C22.2 No. 601.1- Medical Electrical Equipment M90 Information technology Equipment EN 60950-1:2006+A11:2009 EMI - Conducted and radiated emission EN55011, class B Harmonic Current Emissions IEC/EN 61000-3-2, Class A Voltage fluctuations and flicker IEC/EN 61000-3-3, (EN60555-3) Standards Electrostatic Discharge Immunity IEC 61000-4-2 Level 3 RF, Electromagnetic Field Immunity IEC 61000-4-3 Level 2 Electrical Fast Transient/Burst Immunity IEC 61000-4-4 Level 3 Surge Immunity IEC 61000-4-5 Level 2 RF, Conducted Disturbance Immunity IEC 61000-4-6 Level 2 Power frequency Magnetic Field Immunity IEC 61000-4-8 Level 2 Voltage dips, Short Interruptions Immunity IEC 61000-4-11 www.aimtec.com Tel: +1 514 620 2722 Toll free: + 1 888 9 AIMTEC (924 6832) F 052e R7.P 2 of 4 North America only