Alpha Wire 711 Lidgerwood Avenue, Elizabeth, NJ 07207 Tel: 1-800-52 ALPHA (25742), Web: www.alphawire.com Customer Specification PART NO. 6453 Construction Diameters (In) 1) Component 1 1 X 1 PAIR a) Conductor 22 (7/30) AWG TC 0.030 b) Insulation 0.0285 Wall, Nom. Foam HDPE 0.087 (1) Color(s) Pair Color Pair Color Pair Color WHITE/BLUE- 1 BLUE/WHITE c) Cabling 2 COND Cabled (1) Twists: 4.8 Twists/foot (min) 2) Shield: Alum/Mylar Tape, 25% Overlap, Min. a) Foil Direction Foil Facing Out b) Drain Wire 22 (7/30) AWG TC c) Braid TC,65% Coverage, Min. 3) Jacket 0.042 Wall, Nom.,PVC 0.284 (0.297 Max.) a) Color(s) BLACK ALPHA WIRE P/N 6453 1PR 22 AWG EXXXXX SHIELDED (UL) CM OR PLTC SUN RES OR b) Print C(UL) CM --- FT1 CE ROHS Note: Product may have c(UL) or CSA markings depending upon plant of manufacture. Applicable Specifications 1) UL PLTC 60C CM 60C SUN RES 2) CSA International CM 60C FT1 3) CE: EU Low Voltage Directive 2006/95/EC Environmental 1) CE: EU Directive 2011/65/EU(RoHS2): This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011. No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire s web site for RoHS C of C. 2) REACH Regulation (EC 1907/2006): This product does not contain Substances of Very High Concern (SVHC) listed on the European Union s REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha s REACH SVHC Declaration. Properties Physical & Mechanical Properties 1) Temperature Range -20 to 60C 2) Bend Radius 10X Cable Diameter 3) Pull Tension 19.8 Lbs, Maximum Electrical Properties (For Engineering purposes only) 300 V 1) Voltage Rating RMS 2) Characteristic Impedance 120 +/- 10 3) Mutual Capacitance 11 pf/ft 1 kHz, Nominal 4) Ground Capacitance 20.9 pf/ft 1 kHz, Nominal 5) Velocity of Propagation 78 % 6) Conductor DCR 15.1 /1000ft 20C, Nominal 7) OA Shield DCR 4.3 /1000ft 20C, Nominal 8) Current 2.7 amps per conductor 30C, Maximum 9) Attenuation, Max dB/100ft 0.5 1 MHz Other Packaging Flange x Traverse x Barrel (inches) a) 1000 FT 16 x 11 x 8 Continuous length b) 500 FT 12 x 10 x 5 Continuous length c) 100 FT 12 x 4.5 x 3.5 Continuous length Spool dimensions may vary slightly Notes: a) EIA Industrial RS485 cable. www.alphawire.com Alpha Wire 711 Lidgerwood Avenue, Elizabeth, NJ 07207 Tel: 1-800-52 ALPHA (25742)