16 1820 1 2 3 4 5 6 7 8 9 10 12 14 GFR Series - 1 Pole+N, D Trip, 30 mA 277V AC Ground Fault Relay with Overload Protection (RCBO) The GFR Series is a combined Equipment Ground Fault Relay and Supplementary Protector (RCBO), featuring dual pole switching (live and neutral) and designed to provide protection against overloads and AC ground faults (residual current faults) as well as pulsating DC ground faults. Short Circuit Withstand rating is 10kA. Ordering Information Rated Type/ Rated Current Cat. No. Voltage 5.0A GFR2D05030 277V AC Ground Fault Sensing & Relaying Equipment 6.0A GFR2D06030 277V AC E483493 8.0A GFR2D08030 277V AC 10A GFR2D10030 277V AC 12A GFR2D12030 277V AC 13A GFR2D13030 277V AC 15A GFR2D15030 277V AC 16A GFR2D16030 277V AC 20A GFR2D20030 277V AC GFL Series RCBO 25A GFR2D25030 277V AC Overload Trip Curves 30A GFR2D30030 277V AC Characteristics B, C, D 7200 32A GFR2D32030 277V AC 3600 2400 35A GFR2D35030 277V AC 1200 40A GFR2D40030 277V AC 600 480 360 Technical Specification 240 120 Number of Poles 1+N 60 Voltage Rating (maximum) 277V AC 40 Ground Fault Sensitivity Level 30 mA 20 Short Circuit Withstand Rating 30 kA 10 Rated Frequency 50/60Hz 5 Trip Characteristic D 2 2 Cable Size & Tightening Torque Stranded Wire: 16 - 3 AWG (1.5 mm - 25 mm ) 17.5 lb-in (2.0 Nm) 2 2 16 - 10 AWG (1.5 mm - 5.5 mm ) 17.5 lb-in (2.0 Nm) 1 Solid Wire: 2 2 18 - 16 AWG (1 mm - 1.5 mm ) 25 lb-in (2.8 Nm) 0.5 Electrical Life 6000 Switching Operations Mechanical Life 10000 Switching Operations B C D Dimensions 0.1 (to convert to inches multply by 0.03937) 0.05 85mm 45mm 0.01 35 mm 1.05 1.35 Rated current multiple x I n GFR Series RCBO Ground Fault Trip Curve 0.5 0.4 0.2 0.3 0.15 0.1 0.05 17.5mm 0.04 0.03 Weight 217 g 0.02 0.015 0.01 GFR Series RCBO Short Circuit Withstand Rating V I IR Backup 0.005 0.5 1 5 0.85 1.15 20A 10kA None I 1+N Pole Class J Fuse 250A or lower In 277V AC >20A 10kA Altech L Series Branch Circuit Breaker Altech R Series Supplementary Protector 1 35 Royal Road Flemington, NJ 08822-6000 t 908-806-9400 f 908-806-9490 www.altechcorp.com UL 1077 Ground Fault Relay with Overload Protection 71mm 60mm 44mm t(s) Switch time t(s)UL 1077 Ground Fault Relay with Overload Protection GFR Series - 1 Pole+N, D Trip, 30 mA Applicable voltage systems and wiring examples. L1 GFR2 277 V 480 V 480 V L2 277 V 480 V N 277 V L3 L1 GFR2 240 V 400 V 400 V L2 240 V 400 V N 240 V L3 L1 GFR2 120 V 208 V 208 V L2 120 V 208 V N 120 V L3 GFR2 NOTE: Wiring a hot leg/phase to N terminal is not permitted. 2 35 Royal Road Flemington, NJ 08822-6000 t 908-806-9400 f 908-806-9490 www.altechcorp.com 120 V 120 V 240 V L1 N L2 LOAD LOAD LOAD LOAD 1 N LINE N 2