PS-S10 Series Features: Universal AC input / full range Specifications Protections: Short Circuit / Overload / Overvoltage Cooling by free air convection DIN rail mountable Built in DC OK active signal LED indicator for power on No load power consumption < 0.75W 100% full load burn-in test 3 year warranty Cat. No. PS-S1005 PS-S1012 PS-S1015 PS-S1024 OUTPUT DC VOLTAGE 5V 12V 15V 24V RATED CURRENT 2A 0.84A 0.67A 0.42A CURRENT RANGE 0~2A 0~0.84A 0~0.67A 0~0.42A RATED POWER 10W 10W 10W 10W RIPPLE & NOISE (max) 80mVp-p 120mVp-p 120mVp-p 150mVp-p Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1F & 47F parallel capacitor VOLTAGE TOLERANCE 5.0% 3.0% 3.0% 2.0% Tolerance: includes set up tolerance, line regulation and load regulation. LINE REGULATION 1.0% 1.0% 1.0% 1.0% LOAD REGULATION 5.0% 3.0% 3.0% 2.0% SETUP, RISE TIME 500ms, 30ms/230VAC 1000ms, 30ms/115VAC at full load Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. INPUT HOLD UP TIME (Typ.) 120ms/230VAC 25ms/115VAC at full load VOLTAGE RANGE 85~264VAC 120~370VDC FREQUENCY RANGE 47~63Hz EFFICIENCY (Typ.) 77% 81% 81% 84% AC CURRENT (max.) 0.33A/115VAC 0.21A/230VAC INRUSH CURRENT (Typ.) COLD START: 35A/115VAC 70A/230VAC LEAKAGE CURRENT <1mA/ 240VAC PROTECTION OVERLOAD PROTECTION Above 105% rated output power Protection type: Hiccup mode, recovers automatically after fault condition is removed OVERVOLTAGE PROTECTION 5.75~6.75V 13.8~16.2V 17.25~20.25V 27.6~32.4V Protection type: Shut down overvoltage, re-power on to recover OVER TEMPERATURE PROTECTION Power supply shut down at 70C constant current limiting / output voltage goes to 0 re-power on to recover DC OK AKTIV SIGNAL (max.) 3.75~6V (50mA) 9~13.5V (40mA) 11.5~16.5V (40mA) 18~27V (20mA) ENVIRONMENT WORKING TEMP. -20 ~ +70C (Refer to output load derating curve) WORKING HUMIDITY 20 ~ 90% RH non-condensing STORAGE TEMP. / HUMIDITY -40 ~ +85C 10 ~ 95% RH TEMP. COEFFICIENT 0.03% C (0 ~ 50C) VIBRATION Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes MOUNTING Compliance to IEC60068-2-6 SAFETY & EMC SAFETY STANDARDS UL508 EN60950-1 compliant WITHSTAND VOLTAGE I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC EMI CONDUCTION & RADIATION Compliance to EN55011 EN55022 (CISPR22) EN61204-3 Class B HARMONIC CURRENT Compliance to EN61000-3-2,-3 EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11 EN55024 EN61000-6-1 EN61204-3 light industry level criteria A The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. OTHERS MTBF 584K hrs min. MIL-HDBK-217K (25C) DIMENSION 22.5x90x100mm (WxHxD) PACKING 0.17Kg 72pcs / 13.2Kg / 0.91CUFT All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25C of ambient temperature For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power. 62Mechanical Specification 22.5 100 5 5 Terminal Pin. No Assign. (TB1) DC +V -V OK Pin No. Assignment 1 FG 2 AC/N 3 AC/L Terminal Pin. No Assign. (TB2) Pin No. Assignment 4 DC OUTPUT +V 5 DC OUTPUT -V 6 DC OK SIGNAL NL 5 5 Block Diagram RECTIFIERS RECTIFIERS POWER +V EMI I/P & & SWITCHING FILTER -V FILTER FILTER DETECTION CIRCUIT CONTROL O.L.P. O.V.P. Application of DC OK Signal Model R ModelRRModel L R 5V 200 5V 1K 5V 120 R 12V 1.5K 12V 2.4K RelayR L 12V 700 15V 2K 15V 3K 15V 700 5.1V 24V 3.9K 24V 4.7K 24V 1.2K V- V- V- Derating Curve Output Derating VS Input Voltage Ta=25 100 100 Others 90 80 80 5V 60 70 60 40 50 20 40 -20 0 10 20 30 40 50 60 70 (VERTICAL) 85 95 100 115 120 140 160 180 200 220 240 264 Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937. Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 63 90