TR11 Series UL1077 Recognized Supplementary Protector/ Circuit Breaker for Equipment Applications: Protection of Control Transformers, UPS, Power strips, Solenoids etc., against damage due to E209569 up to 12 Amps overload conditions. Current Rating (A) 0.1 - 16A Operating Characteristic Standard Current Rating (A) 0.1, 0.25, 0.5, 0.9, 1.0, 1.2, 1.5, 1.8, 2.0, 2.2, 2.5, 2.7, 3.0, 3.3, 4.0, 5.0, 6.0, 6.5, 7.0, 8.0, 9.0, (min) 60 10.0, 12.0, 15.0, 16.0 30 Rated Voltage 240V AC, 50/60Hz, 50V DC / 24V DC (VDE) 20 (As per EN 60934) Initial insulation resistance (500V DC) > 100 M ohms. 10 Dielectric strength 1.5 KV for One minute. (As per EN 60934) 5 6 In - AC up to 9.0A Overload Switching Capacity (As per EN 60934) 4 I - DC up to 12.0A n 60A AC/DC Max. - from 10.0A to 12.0A 1 Maximum Breaking Capacity 8x I AC/DC for <6.0A n (S) 50 60A AC/DC MAX. for > 6.0A Power Loss 1 - 2 Watts 20 Operating Temperature Maximum 60C Ambient 10 Operational Life at 2xI 1000 Cycles n 5 Rated Conditional Short Circuit 1000 Amps PC 1,240V AC, 24V DC, Ref.: EN60934 Current Capacity I (PC1) SC: 1KA, C1, 240V AC 50V DC nc1 2 Ref.: EN60934 Ref.: CSA22.2 No.235-04, UL-1077 1 Tripping Current Code TC TC 2Ref.: CSA22.2 No. 235-04 Overload Rating OL0 240V AC, 50V DC, Ref.: CSA22.2 No. 235-04 0.5 Application Type General Industrial Ref.: CSA22.2 No. 235-04 Method of Tripping Thermal TO Trip Free 0.2 Type of Actuation Reset Type R 0.1 Application Standards CSA 22.2 No. 235-04, UL-1077, EN 60934 1.05 1.32 23485 10 Weight aprox. 11g Approvals 0.1 - 16.0A 0.5 - 12.0A Multiple of Rated Current 240V AC 50V DC 240V AC 24V DC Rated current < 6 A > 6 A ORDERING INSTRUCTIONS Ambient 23C Temperature TR20 C 63 SB 1 A 7.0A 2 INDICATOR PLATE PRODUCT Time Current Characteristics: TYPE The standard characteristic is valid for ambient temperatures of +23C. If the device is to be used in an ambient CURRENT RATING temperature other than +23C, 3A, 4A, 5A, 6A, 7A, 8A, 10A, 12A, 15A, 10A & 20A allowances must be made when selecting MOUNTING NUT TERMINAL the current rating according to the CONFIGURATION following guidelines: SLIDER COLOR Ambient temp.C -20 -5 0 +10 +20 +30 +40 +50 +60 White with 0 None Correction Factor 0.8 0.88 0.9 0.96 1 1.05 1.12 1.2 1.3 trip indication 1 White, Vertical 2 Black, Vertical 3 White, Horizontal Example: Normal Continuous Current 1.8A 4 Black, Horizontal Ambient Temperature 40C Correction Factor 1.12 Recommended Current Rating 1.8 x 1.12 = 2.016 Select the nearest 2.0A Note: TR11-C Series stocked contact Altech for availability. Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 P 908.806-9400 F 908.806.9490 www.altechcorp.com 80 Earth Leakage UL 1077 ANNEX UL 1077 UL 508 UL 489 Circuit Breakers Equipment Breakers Trip time TR-11 Dimensions & Mounting Options Central Mounting Wing Clips Wing Clip Types Snap Fitting Body Mounting PCB Mounting Slider Printing for Current Rating Slider Color with Trip Band Accessories Dimensions in mm (to convert to inches multiply by 0.03937) Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 P 908.806-9400 F 908.806.9490 www.altechcorp.com 81 Earth Leakage UL 1077 ANNEX UL 1077 UL 508 UL 489 Circuit Breakers Equipment Breakers