SBE 320 / SBX 350 Connectors
- up to 550 Amps
SBE and SBX connectors can integrate up to 8 auxiliary
power / signal contacts along with the two primary power
circuits. Sequencing within auxiliary positions is possible
using the 4 pin lengths available in the 1x4 auxiliary
connector. SBE and SBX offer touch safe housings.
Silver Plated Wire Contacts up to 350 mcm (185 mm)
Allows low resistance UL rated currents up to 350 amps per pole
Up to 8 Auxiliaries
Enables intelligent power switching, CAN and interlock loop
circuitry, as well as power up to 20 amps per pole. Auxiliaries
are all Last-mate/First-break relative to power contacts.
Durable Housings and Contacts
Like all Multipole connectors, the silver plated power contacts
are rated up to 10,000 mating cycles
| SBE 320 / SBX 350 ORDERING INFORMATION |
SBE 320 / SBX 350 Housings
The largest size of SBE , X, O style housing. SBE housings are molded from a chemical
resistant PBT. SBX housings are molded from PC. SBE 320 and SBX 350 housings of
[ 61.9 ]
the same Voltage Color Code cannot be mated. SBX 350 housings do not meet [ 28.6 ]
2.44
1.13
[ 6.7 ]
EN1175-1 requirements for industrial trucks.
0.27
Top View
Description - SBE 320 Part Numbers - - SBX 350 Part Numbers -
Minimum Quantity .......... 100 25 100 25 ...........
Yellow 2-8171G6 E6362 2-7249G6 6362
Orange 2-8171G7 E6339 2-7249G7 6339
[ 83.4 ]
Red 2-8171G3 E6352 2-7249G3 6352
3.28
Gray 2-8171G1 E6350 2-7249G1 6350
[ 15.9 ]
Blue 2-8171G2 E6351 2-7249G2 6351
0.63
Green 2-8171G4 E6353 2-7249G4 6353
Black 2-8171G5 E6361 2-7249G5 6361
[ 125.4 ]
Brown 2-8171G8 E6336 N/A N/A
4.94
Purple 2-8171G9 E6349 N/A N/A
[ 200.0 ]
7.88
Mated Length
[ 33.3 ]
1.31
SBE 320 / SBX 350 Silver Plated Primary Power Wire Contacts
Silver plated contacts offer superior electrical performance and durability up to 10,000 mating cycles. See reducing bushings in
accessory section for smaller wires.
Dimensions
- A - - B - - C - - D -
AWG mm - Loose Piece Part Numbers - inches mm inches mm inches mm inches mm
Minimum Quantity .... 200 150 50 .............................................................................................................
300/350 mcm 150 - 6358-BK 6358 * 3.03 76.96 0.88 22.20 0.75 19.05 1.25 31.80
4/0 120 6356-BK - 6356 * 3.10 78.74 0.75 19.05 0.64 16.26 1.25 31.80
3/0 95 6355-BK - 6355 * 3.10 78.74 0.70 17.78 0.58 14.73 1.25 31.80
2/0 70 6354-BK - 6354 * 3.10 78.74 0.64 16.26 0.49 12.45 1.25 31.80
2 35 6394-BK - 6394 * 3.10 78.74 0.51 12.95 0.38 9.50 1.25 31.80
A
D
* Sold as pairs. 2 parts shipped
for every 1 part ordered.
C
[ 20.6 ]
B
0.81
2019 Anderson Power Products, Inc. All rights reserved. APP, Anderson Power Products, A, SBE, SBO, SBX, PowerMod, Powerpole and the APP Logo are registered
trademarks of Anderson Power Products, Inc.
- 98 -
All Data Subject To Change Without Notice
www.andersonpower.com
SBE 320 DIN Standard Silver Plated Primary Power Wire Contacts
A
Crimp barrel O.D. are compliant with DIN standard tooling. Will also fit into SBX 350 housings. Not recommended
D
for cross mating with above typical contacts for SBE & SBX .
C
Dimensions
Loose Piece - A - - B - - C - - D -
B
AWG mm ----- Part Numbers ----- inches mm inches mm inches mm inches mm
Minimum Quantity ... 200 50 ...............................................................................................................
3/0 95 1341G3-BK 1341G3 * 2.89 73.41 0.78 19.81 0.59 14.99 0.94 23.88
2/0 70 1341G2-BK 1341G2 * 2.74 69.60 0.68 17.27 0.51 12.95 0.79 20.07
[ 20.6 ]
1/0 50 1341G1-BK 1341G1 * 2.65 67.31 0.57 14.48 0.43 10.92 0.79 20.07
0.81
* Sold as pairs. 2 parts shipped for every 1 part ordered.
| SBE 320 / SBX 350 CONNECTOR SPECIFICATIONS |
SBX & SBE SBE Only
Electrical Mechanical
1
Current Rating Amperes UL CSA EN1175-1 Wire Size Range AWG mm
Power Contacts 1/0 - 350 MCM 53.5 to 185 mm
Primary Power (350 MCM) 550 350 320
Auxiliary Contacts 24 -10 AWG 0.25 to 5.3
Powerpole Auxiliary (12 AWG) 20 20 N/A
1x4 Auxiliary (12 AWG) 20 20 N/A
Max Wire Insulation Diameter in mm
PPMX (20 AWG) 5 5 N/A
Power Contact 0.82 * 20.8 *
Powerpole Auxiliary 0.175 4.45
Voltage Rating AC/DC
4 1x4 Auxiliary 0.14 3.6
Primary Power (350 MCM) - 600 - 150
4 PPMX Auxiliary 0.09 2.29
Powerpole Auxiliary (12 AWG) - 600 - 150
1x4 Auxiliary (12 AWG) - 600 - N/A
2
Operating Temperature F C
PPMX (20 AWG) - 600 - N/A
SBX Housing with -4 to 221 -20 to - 105
all Auxiliary
Dielectric Withstanding Voltage
SBE Housing -40 to 221 -40 to 105
Volts AC 2,200
SBX Housing with Powerpole -4 to 221 -20 to - 105
* Average Mated Contact Resistance milliohms
Auxiliary Housings
2 1/2 350 MCM 0.05
SBE Housing with 1x4 -40 to 221 -40 to 105
and PPMX Auxiliaries
Materials
Mating Cycles Silver / Tin Gold
Housings
Power Contacts 10,000 N/A
SBX and Powerpole Polycarbonate
Powerpole Auxiliary 10,000 / 1500 N/A
Auxiliary Housings
1x4 Auxiliary N/A 10,000
SBE , PPMX and 1x4 Polycarbonate/PBT blend
PPMX Auxiliary N/A 5,000
Auxiliary Housings
Average Mating LBF N
Housing Flammability Rating UL IEC (SBE only)
Main Connector Housing 37 165
SBX /SBE 94 V-0 960C (GWFI)
850C (GWIT)
Per Powerpole Connector 5 22
Contact Materials
Per 1x4 Auxiliary Housing 0.7 3
Power Contacts Au plated copper
Per PPMX Housing 4.5 20
Powerpole Auxiliary Au or Sn - copper alloy
Min Contact/Spring 150 667
Retention Force
1x4 Auxiliary Contacts
Powerpole Housing 25 111
Pin Au over NI - copper allow
1x4 Auxiliary Housing 10 44.5
Socket Au over NI - BeCu
PPMX Housing 12 53
Socket Body Sn over Ni, copper alloy
Min Contact/Spring 150 667
Retention Clip Stainless steel Retention Force
PPMX Contacts Gold plated copper alloy Powerpole Housing 25 111
* Not UL rated 1x4 Auxiliary Housing 10 44.5
3
Contact Terminations - Crimp or Hand Solder PPMX Housing 12 53
1x4 Auxiliary Housing 10 44.5
Note 1: See IEC60664-1 for working voltage
PPMX Housing 12 53
Note 2: Amp ratings are stated per position and based on all positions being fully loaded
1 - Based on 195C rated or better cable of the largest size. Properly calibrated APP
recommended tooling and 25C ambient temperature
2 - limited by thermal properties of the connector plastic housing
3 - USE APP recommended tooling only. Alternate tools may adversely affect performance of our connectors along with UL and CSA recognition
4 - Voltage capability of SBE housings is identical to SBX but derated to meet EN1175-1 requirements
* Refer to assembly instructions for using 300 MCM and 350 MCM wire
- 99 -
All Data Subject To Change Without Notice
www.andersonpower.com