Product: 6304UE Security & Sound, 18-6c, BC, CMP Product Description Security & Sound Cable, Plenum-CMP, 6-18 AWG stranded bare copper conductors with Flamarrest insulation, Flamarrest jacket with ripcord Technical Specifications Product Overview Suitable Applications: Security System, Intercom/PA, Audio/Speaker, Power-Limited Controls Construction Details Conductor Element Number of Element Size Stranding Material Conductor(s) 6 18 AWG 7x26 BC - Bare Copper Insulation Element Material Nom. Thickness Color Code Conductor(s) PVC - Polyvinyl Chloride 0.008 in (0.20 mm) Black, Red, White, Green, Brown, Blue Outer Jacket Material Nom. Thickness Nom. Diameter Ripcord PVC - Polyvinyl Chloride 0.015 in (0.38 mm) 0.216 in (5.49 mm) Yes Overall Cable Diameter (Nominal): 0.216 in (5.49 mm) Electrical Characteristics Electricals Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Max. Current Conductor(s) 6.5 Ohm/1000ft (21 Ohm/km) 34 pF/ft (110 pF/m) 3.5 Amps per conductor 25C Voltage UL Voltage Rating 300 V (CMP) Mechanical Characteristics Temperature UL Temperature Operating 75C 0C to +75C Bend Radius Stationary Min. Installation Min. 2.2 in (56 mm) 2.2 in (56 mm) Max. Pull Tension: 134 lbs Bulk Cable Weight: 43 lbs/1000ft (64 kg/km) Standards and ComplianceEnvironmental Suitability: Indoor - Plenum, Indoor Flammability / Reaction to Fire: NFPA 262, UL 910 (Plenum), FT6, IEC 60332-1-2 CPR Compliance: CPR Euroclass: Eca NEC / UL Compliance: Article 800, CMP CEC / C(UL) Compliance: CMP European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) APAC Compliance: China RoHS II (GB/T 26572-2011) Non-Plenum Number: 5304UE History Update and Revision: Revision Number: 0.282 Revision Date: 12-15-2021 Variants Item Color UPC 6304UE 8771000 Natural 612825175520 6304UE 877U500 Natural 612825175513 6304UE 877500 Natural 612825175537 2022 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on anASI basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden s standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden s knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.