LDP200-120 is the first user programmable unit on the market that can supply any voltage between 24 and 120 VDC, offering unmatched flexibility for many applications. Its compact size, high efficiency, excellent reliability together with easy installation makes it ideal for various industrial applications. LDP200-120 is Class I isolation device suitable for SELV and PELV circuitry and is designed to be mounted on DIN rail and installed inside a protective enclosure. High efficiency and compact size Active PFC Digital Control Wide input voltage range 170 550 VAC Wide output voltage range 24 120 VDC, user settable User settable current limitation threshold Remote ON/OFF or other remote control functions MODBUS over RS-485 interface Multiple protections 2 user programmable voltage steps with settable duration Can be used as battery charger (lead acid, nickel, lithium) Can be used for LED lighting Parallelable for power or redundancy (with external ORing Module) Up to 50C operating temperature with no derating Industrial Control Communication Instrumentation Equipment Renewable Energy Systems 2 LDP200-120 LDP200-120 250 - 500 VAC / 250 725 VDC 24 - 120 VDC 4 A max * * 4.0 A 24 VDC, 3 A 48 VDC, or Vout x Iout = 200 W Max. for Vout > 48 VDC Technical parameters are typical, measured in laboratory environment at 25C and 400 VAC / 50 Hz, at nominal values, after minimum 5 minutes of operation. Single or two phases 200 - 500 VAC Input AC Voltage Range Operating 170 - 550 VAC Input DC Voltage Range 250 725 VDC Input Frequency 47 - 63 Hz Vin = 200 VAC 1.4 A Input AC Current Vin = 500 VAC 0.5 A Vin = 250 VDC 1 A Input DC Current Vin = 725 VDC 0.4 A Inrush Peak Current 50 A Standby Power < 4 W Power Factor Correction Active > 0.9 Touch (Leakage) Current 0.4 mA Internal Protection Fuse None, external fuse must be provided It is strongly recommended to provide external MCB 10 A, C curve Recommended External Protection surge arresters (SPD) according to local regulations. Output Power 200 W Rated Voltage 1 V resolution programmable 24 120 VDC Continuous Current or Vout x Iout = max. 200 W for Vout > 48 V 4.0 A 24 VDC / 3.0 A 48 VDC, Overload Limit Vout dependant 4.4 A to 1.9 A Short Circuit Peak Current Vout dependant 4.9 A to 2.2 A Load Regulation 1% 1 Ripple & Noise 200 mVpp Hold up Time 25 ms C.C. / C.V. (setup via front panel or POWERMASTER Battery Charger Function application) Battery Chemistries Overload and short circuit protection Thermal protection Protections Input undervoltage lockout (UVLO) Input overvoltage protection (VDR) 7 segment, 3 digits display 3 programming keys Status Signals ENABLE - isolated remote ON/OFF input, active for 5 30 VDC DC OK - dry contact (NO, 24 VDC / 1A) MODBUS over RS-485 interface, to be used with POWERMASTER or other applications tech.support psbel.com