Features Applications n Service entrance, branch and OEM panels n Hybrid protection technology n Electrical infrastructures n Extremely low leakage current n Equipment and systems n Heavy duty surge protection n Protection from lightning n LED indicators n Protection from AC power-induced n Compact form factor problems n Indoor or outdoor installation 1202 Series Hardwired AC Hybrid Surge Protective Device (H-SPD) General Information Agency Listing The Bourns Model 1202 Series is a Type 1 hardwired hybrid surge protective device Agency Agency Standard targeted for AC infrastructure applications. The hybrid Model 1202 design combines fast File No. responding MOV technology with low leakage GDT technology resulting in reliable and 1449 - 4th long-term performance. E313168 Ed., Type 1 Electrical Characteristics Model No. Characteristic 1202-120S 1202-240S 120 V 120 / 240 V AC AC Electrical Distribution System (Phase) Single Single/Split Nominal (Operating) Voltage 120 V 120 / 240 V AC AC Maximum Operating Voltage MCOV 150 V AC Temporary Overvoltage Withstand U 150 V T AC Nominal Discharge Current in 15 I 10 kA n Applications of 8/20 s Impulse Waveform Overvoltage Protection Rating (3 kA) V 1200 V pr AC Short Circuit Current Rating I 25 kA 230 V sccr AC Mechanical Characteristics How To Order 1202 - xxxx Enclosure......................................................UL 94 5VA rated Polyphenylene/Polystyrene Series Environmental Rating ...............................................................................IP 66 / NEMA 4x Nominal (Operating) Voltage Mounting .............................................................................................................. Bulkhead 120S = 120 V AC Weight .....................................................................................................................0.5 lbs. 240S = 120/240 V AC Disconnection Indicator .......................................................................................... LED off Electrical Connection ........................... 12 AWG solid wiring leads, 24 inches max. length Mechanical Connection to Panel Packaging Specifications ............... Straight nipple with nut for mounting through 1/2-inch Trade Size knockout 1202 Series ...................one unit per box 1/2-inch Trade Size knockout is approximately 0.875 inch Environmental Characteristics Operating Temperature .............................................................................-40 C to +85 C Moisture Sensitivity Level ................................................................................................. 1 ESD Classification (HBM) ................................................................................................. 6 WARNING Cancer and Reproductive Harm - www.P65Warnings.ca.gov *RoHS Directive 2015/863, Mar 31, 2015 and Annex. Specifications are subject to change without notice. Users should verify actual device performance in their specific applications. The products described herein and this document are subject to specific legal disclaimers as set forth on the last page of this document, and at www.bourns.com/docs/legal/disclaimer.pdf. 1202 Series Hardwired AC Hybrid Surge Protective Device (H-SPD) Product Dimensions 59.5 50.0 19.0 (2.3) (2.0) (0.8) 59.5 MM (2.3) DIMENSIONS: (INCHES) Wiring and Protection Modes Line (Black) V Protected Modes Neutral (White) Line 1 to Ground Line 2 to Ground V Line 1 to Line 2 Neutral to Ground Line (Black) Ground (Green) Model 1202-120S = 1 Hot, 1 Neutral, 1 Ground Model 1202-240S = 2 Hot, 1 Neutral, 1 Ground Asia-Pacific: Tel: +886-2 2562-4117 Email: asiacus bourns.com EMEA: Tel: +36 88 885 877 Email: eurocus bourns.com The Americas: Tel: +1-951 781-5500 Email: americus bourns.com www.bourns.com REV. 14 - 12/19 Specifications are subject to change without notice. Users should verify actual device performance in their specific applications. The products described herein and this document are subject to specific legal disclaimers as set forth on the last page of this document, and at www.bourns.com/docs/legal/disclaimer.pdf.