Features Applications Size: 11.8 mm diameter, Telecommunications equipment 17 mm length Industrial equipment/electronics 100 kA surge rating High power handling Low leakage RoHS compliant* UL Recognized 2063 Series High-Current 2-Electrode Gas Discharge Tube Characteristics Test Methods per ITU-T K.12 and IEC 61643-311. Model No. Characteristic 2063-23 2063-25 2063-30 2063-35 2063-42 DC Sparkover 20 % 100 V/s 230 V 250 V 300 V 350 V 420 V (1) Impulse Sparkover 100 V/ s < 600 V < 600 V < 700 V < 800 V < 900 V 1000 V/ s < 700 V < 700 V < 800 V < 900 V < 1000 V Model No. Characteristic 2063-47 2063-60 2063-70 2063-80 DC Sparkover 20 % 100 V/s 470 V 600 V 700 V 800 V (1) Impulse Sparkover 100 V/ s < 900 V < 1100 V < 1200 V < 1300 V 1000 V/ s < 1100 V < 1300 V < 1400 V < 1500 V (1) Impulse Sparkover voltage is de ned as typical values of distribution. (2) Insulation Resistance (IR) ....................................100 / 250 Vdc ........................................................ > 1 G Glow Voltage ...........................................................10 mA ..................................................................... ~ 70 V Arc Voltage ..............................................................1 A .......................................................................... ~ 10 V Glow-Arc Transition Current .................................................................................................................... < 1 A Maximum Capacitance ............................................1 MHz ..................................................................... < 10 pF Maximum Impulse Discharge Current .....................100,000 A, 8/20 s ................................................ 1 operation 60,000 A, 8/20 s ................................................... 5 operations Nominal Alternating Discharge Current ...................60 A, 50 Hz, 1 second ............................................ 1 operation 300 A, 9 cycles ...................................................... 1 operation Impulse Life ............................................................500 A, 10/1000 s .................................................. > 400 operations (3) DC Holdover Voltage ........................................................................................................................... < 150 ms Operating Temperature ............................................................................................................................ -30 to +85 C Storage Temperature ............................................................................................................................... -40 to +115 C Climatic Category (IEC 60068-1)............................................................................................................. 40 / 90 / 21 Notes: UL Recognized component, UL File E313168. At delivery AQL 0.65, level II DIN ISO 2859 (2) DC Sparkover Voltage IR Measuring Voltage 230400 V 100 V 420800 V 250 V (3) Network Applied DC Sparkover Voltage DC Holdover Voltage 230250 V 135 V 300800 V 150 V *RoHS Directive 2015/863, Mar 31, 2015 and Annex. Specications are subject to change without notice. Users should verify actual device performance in their specic WARNING Cancer and Reproductive Harm applications. The products described herein and this document are subject to specic legal disclaimers as set forth on the www.P65Warnings.ca.gov last page of this document, and at www.bourns.com/docs/legal/disclaimer.pdf. *RoHS COMPLIANT2063 Series High-Current 2-Electrode Gas Discharge Tube Product Dimensions How to Order 2063 - xx - A LF Model Number Designator Voltage (Divided by 10) 23 = 230 V 47 = 470 V 25 = 250 V 60 = 600 V 30 = 300 V 70 = 700 V 35 = 350 V 80 = 800 V 42 = 420 V 17.1 0.3 (.673 .012) Leads A = No Leads Packaging (Blank) = Bulk Packaging - 35 pcs./tray (Standard) RoHS Compliancy LF = RoHS Compliant Product Packaging Speci cations Model 2063 ships standard bulk, 35 pcs. per tray 105 pcs. per box. 11.8 0.2 (.465 .008) MM DIMENSIONS: (INCHES) Asia-Paci c: Tel: +886-2 2562-4117 Fax: +886-2 2562-4116 EMEA: Tel: +36 88 885 877 Fax: +36 88 520 211 The Americas: Tel: +1-951 781-5500 Fax: +1-951 781-5700 www.bourns.com REV. E 09/19 Specications are subject to change without notice. Users should verify actual device performance in their specic applications. The products described herein and this document are subject to specic disclaimers as set forth on the last page of this document, and at www.bourns.com/legal/disclaimer.pdf.