Type: LCVR/2 Under and Over Voltage plus Time Delay Terminal Compact 17.5mm DIN rail housing Protection Microprocessor based to IP20 True R.M.S. monitoring Selectable nominal voltages to suit most popular single phase supply voltages Monitors own supply and detects if the set Under or Over voltage trip levels are exceeded Adjustments for Under and Over voltage trip levels Adjustment for Time delay Independent relay outputs - Under voltage monitoring (RLY2) / Over voltage monitoring (RLY1) 2 x SPDT relay output 5A Green LED indication for supply status Dims: to DIN Individual Red LED indication for both relay statuses 43880 W. 17.5mm FUNCTION DIAGRAM TECHNICAL SPECIFICATION Supply/monitoring voltage Un Under and Over Voltage Monitoring (A1, A2): LCVR/2 (LV)* 110, 115V AC LCVR/2 (HV)* 220, 230, 240V AC Frequency range: 48 63Hz * Please state model Supply variation: LV: 70 150V HV: 140 315V AC variant when Overvoltage category: III (IEC 60664) Rated impulse withstand voltage: 4kV (1.2/50S) IEC 60664 ordering Power consumption (max.): 2.5VA Monitoring mode: Under and Over voltage Trip levels: Under 2 : Fixed 2% see below Under: 75 95% of Un Over: 105 125% of Un Measuring ranges: Nominal (Un) Under 2 Under Over LCVR/2 (LV) 110V 70V 83 105V 116 138V 115V 74V 156 198V 218 260V LCVR/2 (HV) 220V 140V 165 209V 231 275V 230V 147V 173 219V 242 288V 240V 153V 180 228V 252 300V INSTALLATION AND SETTING Hysteresis: 2% of trip level (factory set) Setting accuracy: 3% BEFORE INSTALLATION, ISOLATE THE SUPPLY. Repeat accuracy: 0.5% at constant conditions Connect the unit as required. The Connection Diagram below shows a typical installation, whereby the supply to Immunity from micro power cuts: <50ms a load is being monitored by the Voltage monitoring relay. If a fault should occur (i.e. fuse blowing), the relay will Response time: 50ms de-energise and assuming control of the external Contactor, de-energise the Contactor as well. Time delay (t): 0.2 10s ( 5%) Note: actual delay (t) = adjustable delay + response time Applying power. Power on delay (Td): 1s (worst case = Td x 2) Set the Nominal (Un) voltage selector to match that of the voltage being monitored. Reset time: 50 100ms Set the Over % adjustment to maximum and the Under % adjustment to minimum. Set the Delay (t) Power on indication: Green LED to minimum. Relay status indication: Red LED x2 Apply power and the green Power supply LED will illuminate. Both the red RLY1 /RLY2 LEDs will Ambient temperature: -20 to +60C illuminate and corresponding RLY1 and RLY2 relays energise after the short Power on delay (Td). Relative humidity: +95% max. Refer to the Troubleshooting table if the unit fails to operate correctly. Output (15, 16, 18 / 25, 26, 28): 2 x SPDT relay Output rating: AC1 250V 5A (1250VA) Setting the unit (with power applied). AC15 250V 2A Set the Over % and the Under % adjustments to give the required monitoring range. DC1 25V 5A (125W) If large supply variations are anticipated, the adjustments should be set further from the nominal voltage. Electrical life: 150,000 ops at rated load Set the Delay (t) adjustment as required. (Note that the delay is only effective should the supply increase Dielectric voltage: 2kV AC (rms) IEC 60947-1 above or drop below the set trip levels. However, if during an under voltage condition the supply drops below Rated impulse withstand voltage: 4kV (1.2/50S) IEC 60664 nd the 2 under voltage trip level, any set time delay is automatically cancelled and both relays de-energise Housing: Orange flame retardant UL94 immediately). Weight: 90g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct Troubleshooting. surface mounting via 2 x M3.5 or 4BA screws using the black The table below shows the status of the unit during a particular fault condition. clips provided on the rear of the unit. 2 Terminal conductor size 2 x 2.5mm solid or stranded Green LED Red LED Red LED Supply fault Relay RLY1 Relay RLY2 Approvals: Conforms to IEC. CE, and RoHS Compliant. Under voltage condition (during timing) On On Flashing Energised En for delay (t) EMC: Under voltage condition (after timing) On Off Off Energised De-energised Immunity: EN 61000-6-2 Emissions: EN 61000-6-4 Over voltage condition (during timing) On Flashing On En for delay (t) Energised Over voltage condition (after timing) On Off On De-energised Energised Supply < fixed under trip level 2 On Off Off De-energised De-energised CONNECTION DIAGRAM SETTING DETAILS DIMENSIONS 1. Power supply status (Green) 89 (exc. clips) LE D 67.5 2. Relay output / Timing status 45 (Red) LED for Over voltage tr ipping 3. Relay output / Timing status (Red) LED for Under voltage tripping 4. Nominal (Un) voltage Insert screwdriver to release clips se lector 5. Over % trip level adjustment 6. Delay (t) adjustment 7. Under % trip level ad justment Withdraw clips fully when surface mounting scaled as % of the selected 92 (+/- 1mm) nominal voltage Un Above example showing LCVR/2 (HV) all dimensions in mm. Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England LCVR 2-1-A.DOCX XXXXX Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice) however, use of such information shall be entirely at the users own risk. 29 49.5 66.5X-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for Broyce Control manufacturer: Other Similar products are found below : LART 12-230V AC/DC LXCVR 230V LBVR/A 12-24VDC LMCCR-10A LESW 12-230V AC/DC