Energy Management Energy Analyzer Type EM112 Single phase energy analyzer Class 1 (kWh) according to EN62053-21 Class B (kWh) according to EN50470-3 Accuracy 0.5% RDG (current/voltage) Direct current measurement up to 100AAC Backlit LCD display (3x 8-digit) with integrated touch key-pad Energy readout on display: 8 digit Variable readout on display: 4 digit Energy measurement: kWh and kvarh (imported/exported) kWh+ by 2 tariffs System variables, kW, kvar, V, A, PF, Hz, kWdmd, kWdmd peak Self power supply Dimensions: 2-DIN module Protection degree (front): IP51 Pulse output (optional, by open collector PNP) RS485 Modbus port (optional) M-bus port (optional) Digital input (for tariff management) Easy connection or wrong current direction detection Certified according to MID Directive (option PF only): see how to order below Product description Single-phase energy applications up to 100 A the imported one. Housing energy being measured, analyzer with backlit LCD (direct connection), with dual for DIN-rail mounting, with RS485 Modbus port or M-bus display with integrated touch tariff management availability. IP51 front degree protection. port. keypad. Particularly indicated It can measure imported The analyzer is optionally for active energy metering and exported energy or be provided with pulse output and for cost allocation in programmed to consider only proportional to the active How to order EM112-DIN AV0 1 X O1 PF B Certified according to MID Directive, Module B MID and Module D of Annex II, for legal metrology Model relevant to active electrical energy meters (see Annex V, Range code MI003, of MID). Can be used for fiscal (legal) metrology. System Power supply Output Option Measurement Type Selection Range code System Power supply Output AV0: 230VLN AC - 5(100)A 1: 1-phase 2-wire X: Self power supply O1: pulse output (Direct connection) -30% +20% of the S1: RS485 Modbus port rated measuring input AV1: 120VLN AC - 5(100)A M1: M-bus port voltage, 50Hz (Direct connection) Option Measurement PF: Certified according to MID Directive. Can be used for A: The power is always integrated (both in case of fiscal (legal) metrology. positive imported and negative exported power) and the total energy meter is certified according to MID. B: Only the total positive energy meter is certified according to MID. Specification are subject to change without notice EM112 DS 050218 1EM112 How to order EM112-DIN AV0 1 X O1 X STANDARD Model Range code Not certified according to MID Directive. Cannot be used System for fiscal (legal) metrology. Power supply Output Option Type Selection Range code System Power supply Output AV0: 230VLN AC - 5(100)A 1: 1-phase 2-wire X: Self power supply O1: pulse output (Direct connection) -30% +20% of the S1: RS485 Modbus port rated measuring input AV1: 120VLN AC - 5(100)A M1: M-bus port voltage, 45 to 65Hz (Direct connection) Option X: none Specification are subject to change without notice EM112 DS 050218 2