EM11 DIN Energy Management Energy Analyzer Type EM11 DIN Class 1 (kWh) according to EN62053-21 Class B (kWh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy 0.5 RDG (current/voltage) Energy analyzer Instantaneous variables readout: 4 DGT Energies readout: 6 DGT Instantaneous variables: V, A, W, Wdmd, Wdmd max, var, PF, Hz Single phase variables: VLL, VLN, A, VA, W, var, PF Energy measurements: total kWh and kvarh TRMS measurements of distorted sine waves (voltages/currents) Self power supply Dimensions: 1-DIN module Protection degree (front): IP40 1 pulse output on request Other versions available (not certified, option X): see how to order on the next page 1 alarm output on request Certified according to MID Directive (option PF only): see how to order below Product Description One-phase energy analyzer tive energy metering and 32A. Moreover the meter measured or alarm con- with built-in configuration for cost allocation. Housing can be provided with either trol on the available push button and LCD data for DIN-rail mounting, IP40 pulse output proportional instantaneous variables. displaying particularly indi- (front) protection degree. to the active energy being cated for active and reac- Direct connection up to How to order EM11 DIN AV8 1 X O1 PF Certified according to MID Directive, Mod- ule B and Module D of Annex II, for legal Model MID metrology relevant to active electrical Range code energy meters (see Annex V, MI003, of System MID). Can be used for fiscal (legal) metrology. Power supply Output Option Type Selection Range code System Power supply Option AV8: 230V AC - 5(32)A LN 1: 1-phase X: Self power supply PF: Certified according to (direct connection) MID Directive. Can (from 48 to 62Hz). be used for fiscal The instrument Output (legal) metrology. works on the range from -20% to +20% O1: Pulse type (open col- of the measuring lector output) input nominal voltage. NOTE: please check the availability of the needed code on the verification path PF AV8 1 X O1 diagram on left before order. Specifications are subject to change without notice EM11DIN DS ENG 130117 1 Range System Power supply Output OptionEM11 DIN How to order EM11 DIN AV8 1 X O1 X STANDARD Model Range code Not certified according to MID directive. Cannot be System Power supply used for fiscal (legal) metrology. Output Option Type Selection Range code System Power supply Option AV7: 120V AC - 5(32)A LN 1: 1-phase X: Self power supply X: none (direct connection) (from 48 to 62Hz). AV8: 230V AC - 5(32)A LN The instrument (direct connection) Output works on the range from -20% to +20% of the measuring O1: Pulse type (open col- input nominal lector output) voltage. R1: Alarm type (relay output) NOTE: please check the availability of the needed code on the verification path diagrams below before order. X AV7 1 X O1 AV8 1 X O1 X R1 2 Specifications are subject to change without notice EM11DIN DS ENG 130117 Range System Power supply Output Option Range System Power supply Output Option