Receiver for Digital Signals
Du line
Type G 3830 5543
Fieldbus
Installationbus
8-channel receiver
Galvanically separated SPST relay outputs
Load: 8 x 5 A/250 VAC
H8-housing
For mounting on DIN-rail (EN 50022)
LED-indications for supply, Dupline carrier
and outputs
AC or DC power supply
Channel coding by GAP 1605
Product Description Ordering Key
G 3830 5543 024
Dupline receiver. trol of 8 loads of up to 250
Type: Dupline
SPST relay outputs for con- VAC/5 A.
H8-housing
Receiver
No. of channels
Output type
Power supply
Type Selection
Supply Ordering no.
8 channels
5 A/250 VAC
24 VAC G 3830 5543 024
115 VAC G 3830 5543 115
230 VAC G 3830 5543 230
15-30 VDC G 3830 5543 824
Supply Specifications
Power supply AC types Overvoltage cat. III (IEC 60664) Power supply DC type Overvoltage cat. III (IEC 60664)
Rated operational voltage Rated operational voltage
through term. 21 & 22 230 230 VAC, 15% (IEC 60038) through term. 21 & 22 824 15 to 30 VDC (ripple included)
115 115 VAC, 15% (IEC 60038) Ripple 3 V
024 24 VAC, 15% Reverse-polarity protection Yes
Frequency 45 to 65 Hz Rated operational power 1.5 W
Voltage interruption 40 ms Power dissipation 5.5 W
Rated operational power Typ. 7.0 VA Inrush current 1 A
Rated impulse withstand Rated impulse withstand
voltage 230 4 kV voltage 800 V
115 2.5 kV Dielectric voltage
024 800 V Supply - Dupline 200 VAC (rms)
Dielectric voltage Supply - Inputs 4 kVAC (rms)
Supply - Dupline 4 kVAC (rms) Supply - Outputs 4 kVAC (rms)
Supply - Outputs 4 kVAC (rms)
Output Specifications
6
Outputs 8, SPST relays Mechanical lifetime 30 x 10 operations
Isolated in groups of 8 x 1 Electrical lifetime
5
Contact ratings (AgCdO) (micro gap) (at max. load) AC 1 2.0 x 10 operations
Resistive loads AC 1 5 A/250 VAC (1250 VA) Operating frequency 7200 operations/h
DC 1 0.25 A/250 VDC (62 W) Dielectric voltage
or 5 A/25 VDC (125 W) Outputs - Dupline 4 kVAC (rms)
Inductive loads AC 15 2.5 A/230 VAC
Response time 1 pulse train
DC 13 5 A/24 VDC
Specifications are subject to change without notice (08.10.2007) 1
Dupline is a registered trademark. A product of the CARLO GAVAZZI GroupG 3830 5543
Du line
Fieldbus Installationbus
General Specifications Mode of Operation
8-channel receiver with 8 The default setting of the
Output OFF delay
normally open contact out- module is such that upon
upon loss of Dupline carrier 20 ms
puts. Each output may be loss of Dupline carrier all
Power ON delay Typ. 2 s
coded individually by means the outputs go off.
Indication for
of the code programmer
Supply ON LED, green
GAP 1605. For details,
Output connections
Dupline carrier LED, yellow
please refer to the respective
Output ON LED, red (one per output)
Output 1: terminals 29 & 30
data sheet.
Environment Output 2: terminals 31 & 32
Degree of protection IP 20 Output 3: terminals 33 & 34
The outputs are normally off.
Pollution degree 3 (IEC 60664) Output 4: terminals 35 & 36
When a transmitter coded to
Operating temperature -20 to +50C (-4 to +122F) Output 5: terminals 9 & 10
the selected channel is ac-
Storage temperature -50 to +85C (-58 to +185F) Output 6: terminals 11 & 12
tivated, the output turns on
Output 7: terminals 13 & 14
and remains on until the re-
Humidity (non-condensing) 20 to 80%
Output 8: terminals 15 & 16
spective channel becomes
Mechanical resistance
deactivated.
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions
Material
(see Technical information) H8-housing
Weight 800 g
Operation Diagram
Power supply
Dupline carrier
Transmission on channel for output 1
Output 1 (term. 29 & 30)
Transmission on chan. for output 2
Output 2 (term. 31 & 32)
Wiring Diagram Dimensions (mm)
H8-housing
out out out out
5 6 7 8
out out out out
1 2 3 4
Power
supply
S: signal wire
Accessories
DIN-rail FMD 411
For further information seeAccessorie.
2 Specifications are subject to change without notice (08.10.2007)
Dupline is a registered trademark. A product of the CARLO GAVAZZI Group