Dupline Field- and Installationbus Dupline Profibus-DP Gateway Type G 3891 0020 Built-in Dupline channel generator PROFIBUS-DP slave according to EN 50 170 Certified by the PNO PROFIBUS-DP communication speed of up to 12 MBaud Read/control 128 Dupline inputs/outputs through PROFIBUS-DP Split-I/O mode selectable (128 inputs and 128 outputs) Signals from AnaLink sensors available on the DP-network For mounting on DIN-rail (EN 50 022) LED indicators for supply, Dupline carrier and fault AC power supply Product Description Ordering Key G 3891 0020 230 Dupline Channel Generator pliers). Several Dupline gate- Type: Dupline with the function of a PROFI- ways can be connected to the Type no. BUS-DP slave. This means same PROFIBUS-DP network. Supply that the 128 Dupline I/Os (incl. The unit is certified by PNO AnaLink) can be read/control- (Profibus Nutzer Organisation) led by PROFIBUS-DP mas- which ensures compatibility Type Selection ters (PLCs, PC interface and interoperability with other cards, etc. from various sup- PNO-certified products. Supply Ordering no. 115/230 VAC G 3891 0020 230 Input/Output Specifications PROFIBUS-DP RS 485 Adjustments 9-pole female SUB-D 2 x 10 pos. rotary switchPROFIBUS Slave Address Pin assignment A Pin 8 Range 02 to 99 B Pin 3 1 x 16 pos. rotary switchNo. Dupline channels RTS Pin 4 8 .. 128 in steps of 8 +5V Pin 6 DIP-switch 1 Dupline mode (Normal/Split I/O) GND Pin 5 DIP-switch 2 Dupline data transfer mode Baudrate Auto detection DIP-switch 3 Analog protocol Cable length 100 m 12 MBaud DIP-switch 4 Not used 200 m 1.5 MBaud Approvals 1200 m 93.75 kBaud PROFIBUS operability PNO Up-date time (128 digital I/O) Typ. 200 s at 12 MBaud (Profibus Nutzer Organisation) Typ. 1.6 ms at 1.5 MBaud Electrical safety UL, CSA Dielectric voltage Conformity PROFIBUS-DP Dupline 4 kVAC (rms) CE EMC Industrial Environment PROFIBUS-DP ID-no. 6590 GSD-file GDUP6590.GSD Dupline Output voltage 8.2 V Output current 100 mA Short-circuit protection Yes Output impedance 15 Sequence time 8 digital I/O 15.2 ms 128 digital I/O 132.3 ms AnaLink value update time 8 signals 3.9 s 128 signals 33.8 s Specifications are subject to change without notice 1G 3891 0020 General Specifications Supply Specifications Power supply Overvoltage cat. III (IEC 664) Power ON delay < 2.5 s until start of Rated operational voltage Dupline carrier. through term. 21, 22, 23 & 24 See wiring diagram < 40 s until correct reading 230 230 VAC 15% (IEC 38) of AnaLink values 115 115 VAC 15% (IEC 38) Indication for Frequency 45 to 65 Hz Supply ON LED, green Rated operational power 11 VA Dupline carrier LED, yellow Rated impulse withstand Fault LED, red voltage 230 4 kV Environment 115 2.5 kV Degree of protection IP 20 Dielectric voltage Pollution degree 3 (IEC 664) Supply - Dupline 4 kVAC (rms) Operating temperature 0 to +50C (+32 to +122F) Supply - RS 485 4 kVAC (rms) Storage temperature -20 to +85C (-4 to +185F) Humidity (non-condensing) 20 to 80% RH Mechanical resistance Shock 15 G (11 ms) Vibration 2 G (6 to 55 Hz) Dimensions Material H8-housing Weight 540 g Wiring Diagrams Power supply Power supply 230 VAC 115 VAC Mode of Operation The Dupline PROFIBUS-DP sation) that ensures compati- the range 02..99. (00..01 are Consequently, a Dupline-output Gateway is a Dupline channel bility with other PNO-certified reserved). Each module con- can either be activated through generator with the function of products. nected to PROFIBUS-DP must the output-data received on a PROFIBUS-DP slave accor- have a unique slave address PROFIBUS-DP or by an active ding to EN 50 170. This means Configuration Switches which enables the PROFI- Dupline input coded for the that the 128 Dupline I/Os The unit is equipped with the BUS-DP Master to access the same Dupline-address. (incl. AnaLink) can be read/ following configuration switch- modules individually. In Split I/O mode, the controlled by PROFIBUS-DP es (see also Switch settings): Dupline-inputs and Dupline- masters like PLCs and PC 1 x DIP-switch for selection of outputs are treated indepen- interface-cards from many 1 x 16-position rotary-switch Dupline Operation Mode. In dently by the channel gene- different suppliers. Several for selecting the Number of Normal mode, Dupline ope- rator. If e.g. an input coded Dupline gateways can be Dupline channels in the rates as a peer-to-peer sys- for B5 is activated, the connected to the same PRO- range 8..128 (in steps of 8). tem where the channel gene- Gateway will make the infor- FIBUS-DP network and ope- The selected letter indicates rator automatically establishes mation available on PROFI- rate together with other PRO- the last channel group avail- a connection between Dup- BUS-DP (like in normal FIBUS-DP modules like ope- able on Dupline. If e.g. H is line-inputs and Dupline-out- mode), but it will not auto- ratorpanels, MMIs, frequency selected, the 64 channels in puts which are coded to the matically activate the Dupli- inverters, I/O-modules etc. groups A..H will be available. same Dupline-address. If e.g. ne-output(s) coded to B5. an input coded for B5 is acti- The Dupline-outputs are con- The Dupline PROFIBUS-DP 2 x 10-position rotary switch vated, the output(s) coded for trolled exclusively through the Gateway is approved by the for selection of the PROFI- B5 will also be activated. output data received on PNO (Profibus Nutzer Organi- BUS-DP Slave Address in PROFIBUS-DP. 2 Specifications are subject to change without notice