Dupline
Transmitter with Built-in Temperature Sensor
Type G 8911 1010
AnaLink temperature transmitter
with built-in Pt 1000 sensor
Temperature range: -30C to +60C (-22 to +140F)
Uses only 1 channel
Channel coding by GAP 1605
M12 connection
Easily mountable
Supplied by Dupline
Product Descrip tion Ordering Key
G 8911 1010
The sensor is mounted right etc. The sen sor meas ures the
Type: Dupline
at the loca tion where the tem- temper a ture and transmits
Type
perature is to be meas ured, the value to the control ler G
e.g. freezer cabinets in super 3890 0030, which then per -
mar kets, cold storage rooms forms the logging and alarm -
ing.
Type Selection General Speci fi ca tions
Supply Ordering no.
Channel programming By GAP 1605
1 channel
Channel assignment 1 channel,
Pt 1000 sensor
freely programmable
Environment
By Dupline G 8911 1010
Degree of protection IP 67
Operating temperature -30 to +60C (-22 to +140F)
Storage temperature -55 to +85C (-67 to +185F)
Supply Speci fi ca tions
Mechanical resistance
Power supply Supplied by Dupline Shock 15 G (11 ms)
Rated operational current Typ. 800 A Vibration 2 G (6 to 55 Hz)
Connection M12 plug
Housing Flat-pack
Material Housing Polycarbonate
Plug Nylon
Colour Light grey
Dimensions (l x w x d) 67 x 35 x 15 mm
Mounting Direct wall mounting*)
*) To measure the air temperature, the sensor should not be
wall-mounted, but should be exposed to air flow.
Sensor Speci fi ca tions
Sensor Pt 1000 (built-in)
Time constant Typ. 450 s
Temperature measuring
(air flow = 0 m/s)
range -30 to +60C (-22 to +140F)
Typ. 350 s
Temperature probe Pt 1000 (built-in)
(air flow = 1 m/s)
Accuracy See curve below
Resolution 8 bits (approx. 0.35 K/LSB)
Max. error (C)
1,5
1,0
0,5
0
Temp. (C)
-30 -20 -10 0 10 20 30 40 50 60
Specifications are subject to change without notice (19.10.2015) 1 G 8911 1010
Distance versus No. of Sensors Dimensions
DC loop
resistance ()
Example: Max. distance for 75 sen-
sors D 8911 1010: 75 x 0.8 mA = 60
mA loop resistance ~ 35 . If 1.5
2
mm ca ble @ 12 /km is used, the
distance is:
35
= 1.45 km max.
2 x 12 /km
Dupline load (mA)
from AnaLink
sensors
Connections Accessories
Coding cable GTS-CAB*
M12 plug with terminals Pin 1: Dupline D+
Angular M12 plug CONM14NF-A
Pin 4: D-
Straight M12 plug CONM14NF-S
Cable with angular plug CONM13NF-A**
Cable with straight plug CONM13NF-S**
Standard cable with
M12 plug (IEC 60947-5-2)
* Delivered with the G 3890 0030.
with 4 wires: Brown: Dupline (1) D+
** Indicate length 2 m or 5 m.
Black: (4) D-
Blue: (3) D-
White: (2) D-
with 3 wires (1-3-4): Brown: Dupline (1) D+
Black: (4) D-
Blue: (3) D-
with 2 wires (1-4) Brown: Dupline (1) D+
Blue: D-
Note: All wires must be connected.
2 Specifications are subject to change without notice (19.10.2015)