WM30 96
Energy Management
Smart Modular Power Analyzer
Type WM30 96
Class 0.5S (kWh) according to
EN62053-22
Class C (kWh) according to EN50470-3
Class 2 (kvarh) according to EN62053-23
Accuracy 0.2% RDG (current/voltage)
Instantaneous variables readout: 4x4 DGT
Energies readout: 9+1 DGT
System variables: VLL, VLN, A, VA, W, var, PF, Hz,
Phase-sequence-asymmetry-loss.
Single phase variables: VLL, VLN, AL, An (calculated),
VA, W, var, PF
Both system and single phase variables with average
and max calculation
Harmonic analysis (FFT) up to the 32nd harmonic
(current and voltage)
One RS232 and RS485 port (on request)
Energy measurements (imported/exported): total and
Communication protocol: MODBUS-RTU
partial kWh and kvarh
MODBUS TCP/IP Ethernet port (on request)
Energy measurements according to ANSI C12.20 CA
BACnet-IP over Ethernet port (on request)
0.5, ANSI C12.1 (revenue grade)
BACnet MS/TP over RS485, BTL approved (on request)
Run hours counter (8+2 DGT)
Ethernet/IP port, ODVA approved (on request)
Real time clock function
Profibus DP V0 port (on request)
Application adaptable display and programming
Up to 2 digital outputs (pulse, alarm, remote control)
procedure (Easyprog function)
(on request)
Universal power supply: 24-48 VDC/AC, 100-240 VDC/AC
Up to 4 freely configurable virtual alarms
Front dimensions: 96x96 mm
Up to 2 analogue outputs (+20mA, +10VDC) (on request)
Front protection degree: IP65, NEMA4X, NEMA12
Product Description
How to order
WM30-96 AV5 3 H R2 A2 S1 XX
Model
Three-phase smart power either for pulse proportional to the
analyzer with built-in advanced active and reactive energy being Range code
configuration system and LCD
measured or/and for alarm outputs.
System
data displaying. Particularly The instrument can be equipped
Power Supply
recommended for the with the following modules: RS485/
A Outputs
measurement of the main RS232, Ethernet, BACnet-IP,
B Outputs
electrical variables. WM30 is BACnet MS/TP or Profibus DP
Communication
based on a modular housing for
V0 communication ports, pulse
Option
panel mounting with IP65 (front) and alarm outputs. Parameters
protection degree. Moreover, programming and data reading can
the analyzer can be provided be easily performed by means of
with digital outputs that can be WM3040Soft.
Type Selection
Range codes System Power supply A Outputs
AV4: 400/690V AC
LL
3: balanced and H: 100-240 +/-10% (90 XX: none
1(2)A
unbalanced load: to 255) VDC/AC O2: Dual channel static
V : 160V to 480V
LN LN
3-phase, 4-wire; (50/60 Hz) output
V : 277V to 830V
LL LL
3-phase, 3-wire; L: 24-48 +/-15% (20 to R2: Dual channel relay
AV5: 400/690V AC
LL
2-phase, 3-wire; 55) VDC/AC output
5(6)A
1-phase, 2-wire (50/60 Hz)
V : 160V to 480V
LN LN
V : 277V to 830V
LL LL
Options Communication B Outputs
AV6: 100/208V AC
LL
5(6)A
XX: none XX: none XX: none
V : 40V to 144V
LN LN
S1: RS485/RS232 port A2: Dual channel 20mA
V : 70V to 250V
LL LL
E2: Ethernet / Internet DC output
AV7: 100/208V AC
LL
port V2: Dual channel 10V
1(2)A
B1: BACnet (IP) over DC output
V : 40V to 144V
LN LN
Ethernet
V : 70V to 250V
LL LL
B3: BACnet (MS/TP)
over RS485
E6: Ethernet/IP port
P1: Profibus DP/V0 port
Specifications are subject to change without notice WM30 96 DS 310117 1WM30 96
Position of modules and combination
Ref Description Main features Part number Pos. A Pos. B Pos. C
Inputs/system: AV5.3
1 WM30 AV5 3 H
Power supply: H
Inputs/system: AV6.3
2 WM30 AV6 3 H
Power supply: H
Inputs/system: AV4.3
3 WM30 AV4 3 H
Power supply: H
Inputs/system: AV7.3
4 WM30 AV7 3 H
Power supply: H
WM30 base provided with display,
power supply, measuring inputs
Inputs/system: AV5.3
WM30 AV5 3 L
Power supply: L
Inputs/system: AV6.3
WM30 AV6 3 L
Power supply: L
Inputs/system: AV4.3
WM30 AV4 3 L
Power supply: L
Inputs/system: AV7.3
WM30 AV7 3 L
Power supply: L
2-channel
5 Dual relay output (SPDT) M O R2 X
Alarm or/and pulse output
2-channel
6 Dual static output (AC/DC Opto-Mos) M O O2 X
Alarm or/and pulse output
7 Dual analogue output (+20mADC) 2-channel M O A2 X
8 Dual analogue output (+10VDC) 2-channel M O V2 X
9 RS485 / RS232 port module Max. 115.2 Kbps M C 485 232 X
10 Ethernet port module RJ45 10/100 BaseT M C ETH X
11 BACnet-IP port module Based on Ethernet bus M C BAC IP X
12 BACnet-MS/TP port module Over RS485 M C BAC MS X
13 Ethernet/IP Based on Ethernet M C E I X
Profibus DP V0
14 Profibus module M C P B X
Over RS485
NOTE:
The position of the modules shall respect the sequence A-B-C.
Possible arrangements are M, M-A, M-B, M-C, M-A-B, M-A-C,
M-B-C and M-A-B-C where M is the basic module.
It is possible to use the WM30-96 without any additional
module as a simple indicator.
2 Specifications are subject to change without notice WM30 96 DS 310117