Solid State Relays
1-Phase with Heatsink and Integrated Fuse
Type RGC1F
35 mm product width
Solid state contactor with integrated fuse
AC zero cross switching
Operational voltage: up to 600 VAC
Rated load currents of 20 AAC, 30 AAC and 40 AAC
Control voltage: 4.5 - 32 VDC
Integrated voltage transient protection with varistor
Detection of SSR and load mulfunction (RGC1FS)
Alarm output signal (RGC1FS)
100 kA short circuit current rating
Product Description
Ordering Key
RGC 1 F A 60 D 30 GG E
This solid state contactor The front panel can be opened Solid state relay
includes three functions in one for easy access of the fuse Number of poles
housing: power switching, and the fuse holder accepts Integrated fuse
short circuit protection by fuses from a wide range of Switching mode
semicondcutor fuse and sys- manufacturers. Alarms (in
Rated operational voltage
tem monitoring. RGC1FA is RGC1FS) are indicated by a
Control voltage
the version including the pow- red LED on the front and a sig-
Rated operational current
erswitch and the fuse version nal which is normally closed.
Connection type for control and power
with a fuse while the RGC1FS Product width is 35 mm for the
Output connection configuration
includes also the monitoring whole range and covers up to
function which detects load, 600 VAC and 40 AAC.
fuse and SSR faults. Specifications stated at 25C
unless specified.
Ordering Key
Type Integrated Mode Rated Control Rated Connection Connection
fuse voltage voltage current control/ power configuration
RGC1 F A: Zero cross 60: 600 VAC D: 20: 20 AAC G: Box Clamp E: Contactor
switching + fuse 4.5 - 32 VDC 30: 30 AAC
+ fuse holder 40: 40 AAC
S: Zero cross switching
+ fuse + fuse holder
+ system monitoring
Warning
- Risk of electric shock
- Do not open fuse panel when the product is in operation
- Switch off the panel before doing any maintenance on the product. Panel should be closed before restarting operation
- Failure to follow these instructions may result in serious injury (or worse) and/or equipment damage
Selection Guide
Rated output voltage Options Control voltage Rated operational current at 40C
20 AAC 30 AAC 40 AAC
600 VAC Fuse Only 4.5 -32 VDC RGC1FA60D20GGE RGC1FA60D30GGE RGC1FA60D40GGE
600 VAC Fuse + Sensing 4.5 -32 VDC RGC1FS60D20GGE RGC1FS60D30GGE RGC1FS60D40GGE
Specifications are subject to change without notice (31.10.2018) 1RGC1F
Output Voltage Specifications
Operational Voltage Range (+10%, -15% on max) 42-600 VAC
Blocking Voltage 1200 Vp
Internal Varistor 625 V
General Specifications
Supply Specifications (A1+, A2- for RGC1FS)
1
Latching voltage Rated supply voltage, U 24 VDC -15%, +20%
s
(across L1-T1) 20 V according to EN61131-2:2003
Operational frequency Max input current 80 mA during normal conditions
range 45 to 65 Hz
20 mA during alarm conditions
Power factor 0.5 at rated voltage
Touch Protection IP20
Alarm Output Specifications (OUT for RGC1FS)
LEDs Control ON: Green, full intensity
RGC1FS Supply ON: Green, half intensity
Type PNP open Collector
RGC1FS Fault: RED
Normally closed
Pollution degree 2
Rating (@ 40C) 50 mADC, 35 VDC
(non-conductive pollution with
possibilities of condensation)
Over-voltage category III (fixed installations)
Isolation
Input to Output 4000Vrms
Input & Output to Case 4000Vrms
Output Specifications
RGC1F..20 RGC1F..30 RGC1F..40
Rated operational current
2
AC-51 rating @ Ta=40C (IEC60947-4-3 / UL508) 20 AAC 30 AAC 40 AAC
AC-53a rating @ Ta=40C (IEC60947-4-2 / UL508) 4.7 AAC 6 AAC 8 AAC
2, 3
Number of motor starts (x:6, Tx:6s, F:50%) at 40C 30 30 30
Min. operational current 0.2 A 0.2 A 0.2 A
2 2 2 2
I t of integrated fuse @ 690V (size: 14 x 51mm) 740 A s 1400 A s 3100 A s
Critical dv/dt (@ Tj init = 40C) 1000 V/s 1000 V/s 1000 V/s
Motor Ratings: HP (UL508) / kW (EN/IEC60947-4-2) @ 40C
115 VAC 230 VAC 400 VAC 480 VAC 600 VAC
RGC1F..20 1/6 HP / 0.18 kW 1/3 HP / 0.37 kW 3/4 HP / 0.75 kW 1 HP / 1.1 kW 1-1/2 HP / 1.1 kW
RGC1F..30 1/4 HP / 0.25 kW 1/2 HP / 0.56 kW 1 HP / 1.1 kW 2 HP / 1.5 kW 2 HP /1.5 kW
RGC1F..40 0.37 kW 0.75 kW 1.5 kW 1.5 kW 2.2 kW
1: DC voltage to be supplied by a Class 2 power source
2: Refer to Derating curves
3: x: multiple of AC-53a current rating, Tx: duration of current surge, F: duty cycle
2 Specifications are subject to change without notice (31.10.2018)