Solid State Relays
1-Phase with Integrated Heatsink
Proportional Switching Controllers
Types RGC1P..AA.., RGC1P..V..
1-pole analog switching AC solid state contactors
Selectable mode of operation:
- Phase Angle
- Full Cycle x1, x4, x16
- Advanced Full Cycle
- Soft Starting
Rated operational voltage: up to 660 VAC
Rated operational current: up to 63 AAC
Control inputs: 4-20 mA, 0-5 V, 1-5 V, 0-10 V, external
potentiometer
Integrated varistor protection on output
Load ON LED indication
100kA short circuit current rating according to UL508
DIN or panel mount
Product Description Ordering Key
RGC 1 P 60 V 42 E D _
The RGC1P is a series of solid advanced full cycle control Solid state relay
state contactors (with integrat- specific for short wave infrared
Number of poles
ed heatsink) that give the pos- heaters and soft starting for
Type of switching
sibility to control output power limiting inrush current of loads
Rated operational voltage
of 1-phase loads with an ana- having a high temperature
Control input
log control input. Input types coefficient.
Rated operational current
cover a wide range of current
Configuration layout
and voltage ranges. Local set- The output of the RGC1P is
External supply
ting by an external potentiome- protected against overvoltages
ter is possible. Switching by means of an integrated
Options
modes, selectable through a varistor across the output. Two
front knob, allow phase angle front LEDs indicate the status
control, full cycle control, of the load and control.
Specifications are at a surrounding temperature of 25C unless
otherwise specified.
Type Selection
2
SSR with Type of Rated voltage Control Connection External Options
Rated current
1
heatsink switching (Ue), Blocking input configuration supply (Us)
@40C, It
voltage
RGC1: P: Proportional 23: 85 - 265 VAC, AA: 12: 15 AAC, 1800 As E: Contactor D: 24 VDC / AC T: Tamper proof
1-pole 800 Vp 4-20 mADC 30: 30 AAC, 1800 As A: 90 - 250 VAC cover & securness
switching 42: 43 AAC, 18000 As tie included in
48: 190 - 550 VAC, V: 50: 50 AAC, 3200 As packaging
1200 Vp 0-5 VDC 62: 63 AAC, 18000 As
1- 5 VDC
60: 410 - 660 VAC, 0-10 VDC
1200 Vp External
potentiometer
1: V control input versions require an external supply Us
2: Refer to Current Derating
Specifications are subject to change without notice (02.04.2018) 1RGC1P..AA, RGC1P..V
Selection Guide
Output Control External Power Rated operational current @ 40C (It)
voltage, input supply, connection Product width
Ue Us
15 AAC 30 AAC 43 AAC 50 AAC 63 AAC
(1800 As) (1800 As) (18000 As) (3200 As) (18000 As)
35 mm 35 mm 35 mm 70 mm 70 mm
85 - 265 VAC AA:
- Screw RGC1P23AA12E RGC1P23AA30E - - -
RGC1P23AA42E
4-20 mADC
Box - - RGC1P23AA50E RGC1P23AA62E
RGC1P23AA42ET
V: 24 VDC/AC Screw RGC1P23V12ED RGC1P23V30ED - - -
RGC1P23V42ED
0-10V, 0-5V,
Box - - RGC1P23V50ED RGC1P23V62ED
RGC1P23V42EDT
1-5VDC, pot
90-250 VAC Screw RGC1P23V12EA RGC1P23V30EA - - -
Box - - RGC1P23V42EA - RGC1P23V62EA
190 - 550 VAC AA:
Screw RGC1P48AA12E RGC1P48AA30E - - -
-
RGC1P48AA42E
4-20 mADC
Box - - RGC1P48AA50E RGC1P48AA62E
RGC1P48AA42ET
V:
24 VDC/AC Screw RGC1P48V12ED RGC1P48V30ED - - -
0-10V, 0-5V,
Box - - RGC1P48V42ED RGC1P48V50ED RGC1P48V62ED
1-5VDC, pot
90-250 VAC Screw RGC1P48V12EA RGC1P48V30EA - - -
- - RGC1P48V42EA - RGC1P48V62EA
Box
410 - 660 VAC AA:
- Screw - RGC1P60AA30E - - -
4-20 mADC
- - RGC1P60AA42E - RGC1P60AA62E
Box
V:
24 VDC/AC Screw - RGC1P60V30ED - - -
0-10V, 0-5V,
Box - - RGC1P60V42ED - RGC1P60V62ED
1-5VDC, pot
90-250 VAC Screw - RGC1P60V30EA - - -
Box - - RGC1P60V42EA - RGC1P60V62EA
General Specifications
RGC1P..AA RGC1P..V
Operational frequency range 45 to 65 Hz 45 to 65 Hz
Power factor > 0.7 @ rated voltage > 0.7 @ rated voltage
Touch Protection IP20 IP20
3
LED status indication
Green Control input Control input
<4 mA, flashing 0.5s ON, 0.5s OFF 0 V, flashing 0.5s ON, 0.5s OFF
>4 mA, fully on, intensity varies with input >0 V, fully ON
Supply ON (Us) Supply ON (Us)
n/a Flashing 0.5s ON, 0.5s OFF
Yellow Load ON Load ON
Pollution degree 2 (non-conductive pollution with 2 (non-conductive pollution with
possibilities of condensation) possibilities of condensation)
Rated impulse withstand voltage, Uimp 6 kV (1.2/50s) 6 kV (1.2/50s)
Over-voltage category III (fixed installations) III (fixed installations)
Isolation
L1, T1, A1, A2, A3, POT, GND, Us to case 4000 Vrms 4000 Vrms
L1, T1 to A1, A2, A3, Pot, GND, Us 2500 Vrms 2500 Vrms
Us to A1, A2, A3, POT, GND n/a n/a (..V..ED)
1500 Vrms (..V..EA)
3: Refer to LED Indications section
2 Specifications are subject to change without notice (02.04.2018)