Solid State Relays Analog Full Cycle Switching Type RN.F AC solid state relay, 1- and 2-poles Analog switching for resistive loads (heating) 4-20 mA or 0-10 V controls Rated operational current: 1-pole : 30A and 50A 2-pole : 2 x15A and 2 x 25A Rated operational voltage up to 480 VAC LED-indication for normal operation and alarm status IP 20 protection DIN-rail mountable Product Description Ordering Key RN 1 F 40 V 30 The analog switching relay pro- principle operates with zero Solid State Relay vides a number of full cycles, switching, thus ensuring a Number of poles evenly distributed over a fixed reduced level of radiated and Switching type period, depending of the con- wire conducted noise. The 2- Rated operational voltage trol input. The input of 4-20 mA pole type has alarm LED indi- Control signal or 0-10 VDC respectively, cation by loss of master Rated operational current corresponds to zero and full phase. The analogue Full output within a period of 1.28 s Cycle Switching is not recom- 50 Hz (1.07 s 60 Hz). This mended for light control due principle makes the transfer to light-flickering. characteristics fully linear. The Type Selection, 1-Pole Rated Control Control Rated operational current operational voltage input supply 30 A 50 A 120 VAC 4-20 mA RN 1F12I30 RN 1F12I50 0-10 VDC 12-32 VDC, 24 VAC RN 1F12V30 RN 1F12V50 230 VAC 4-20 mA RN 1F23I30 RN 1F23I50 0-10 VDC 12-32 VDC, 24 VAC RN 1F23V30 RN 1F23V50 480 VAC 4-20 mA RN 1F48I30 RN 1F48I50 0-10 VDC 12-32 VDC, 24 VAC RN 1F48V30 RN 1F48V50 Type Selection, 2-Pole Rated Control Control Rated operational current operational voltage input supply 30 A Total (2 x 15A) 50 A Total (2 x 25A) 120 VAC 4-20 mA RN 2F12I30 RN 2F12I50 0-10 VDC 12-32 VDC, 24 VAC RN 2F12V30 RN 2F12V50 230 VAC 4-20 mA RN 2F23I30 RN 2F23I50 0-10 VDC 12-32 VDC, 24 VAC RN 2F23V30 RN 2F23V50 480 VAC 4-20 mA RN 2F48I30 RN 2F48I50 0-10 VDC 12-32 VDC, 24 VAC RN 2F48V30 RN 2F48V50 Specifications are subject to change without notice (20.08.2012) 1RN 1F General Specifications RN.F12... RN.F23... RN.F48... Operational voltage range 85 to 140 VAC 85 to 265 VAC 190 to 530 VAC Blocking voltage 800 V 800 V 1000 V p p p Varistor voltage 275 VAC 275 VAC 510 VAC Zero voltage turn-on < 10 V < 10 V < 20 V Operational frequency range 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz Power factor at rated voltage 0.9 0.9 0.9 Average output power 0 to 100% 0 to 100% 0 to 100% Output power resolution 1/64 of 100% 1/64 of 100% 1/64 of 100% Approvals UL, cUL, CSA UL, cUL, CSA UL, cUL, CSA CE-marking Yes Yes Yes Norms fulfilled EN 60947-1 Low-voltage switchgear and control gear. Part 1- General Rules. EN 61000-6-1 Generic Immunity Standard. Residential, Commercial & Light Industry Environment EN 61000-6-2 Generic Immunity Standard. Industrial Environment Input Specifications RN.F..I.. RN.F..V.. Current controlled input Voltage controlled input Control current range 4 - 20 mA Supply voltage range 21 - 27 VAC, 12 - 32 VDC Allowable input current 50 mA Supply current 30 mA 24 VAC/32 VDC Reverse polarity protected Yes Control voltage range 0 - 10 V Voltage drop 10 VDC 20 mA Control input current 0.1 mA 10 VDC Output Specifications RN.F..30 RN.F..50 Rated operational current RN1F.. AC51 Ta=30C 30 A 50 A Ta=40C 30 A 50 A Ta=50C 23 A 38 A Ta=60C 20 A 30 A RN2F.. AC51 Ta=30C 30 A total sum (2 x 15A) 50 A total sum (2 x 25A) Ta=40C 30 A total sum (2 x 15A) 50 A total sum (2 x 25A) Ta=50C 23 A total sum (2 x 11.5A) 38 A total sum (2 x 19A) Ta=60C 20 A total sum (2 x 10A) 30 A total sum (2 x 15A) Zero crossing detection Yes Yes Min. operational current (per pole) 500 mA 1.8 A Rep. overload current t=1 s (Tj init.=25C) 55 A (rms) 125 A (rms) Non-rep. surge current t=10 ms (Tj init.=25C) < 325 A < 600 A p p Off-state leakage current, rated voltage and frequency (Tj.=125C, max.) < 6 mA < 6 mA 2 2 2 I t for fusing t=10 ms 525 A s 1800 A s Critical dV/dt off-state 500 V/s 500 V/s Thermal Specifications RN.F..30 RN.F..50 Operational temperature -30 to +70C (-22 to +158F) -30 to +70C (-22 to +158F) Storage temperature -30 to +100C (-22 to +212F) -30 to +100C (-22 to +212F) Junction temperature < 125C (257F) < 125C (257F) R junction to ambient (AC load) 2.8 K/W 1.7 K/W th 2 Specifications are subject to change without notice (20.08.2012)