CHB150W12 SERIES 150 WATT 12:1 INPUT ISOLATED DC-DC CONVERTER Features Efficiency Up to 91% Fixed Switching Frequency Regulated Outputs Remote On/Off Fully protected (OTP/OCP/OVP/UVLO) 3000Vac I/O Isolation Operating Case Temperature -40 to +100 Half Brick Size Meet Industrial Standard 2.282.40x0.50 CB Test Certificate IEC62368-1 EN50155 Compliant with External Circuits UL62368-1 2nd (Reinforce Insulation) Approval Shock & Vibration EN50155 (EN61373) Compliant Fire & Smoke EN45545-2 Compliant 5000m Operating Altitude OUTPUT CURRENT INPUT CURRENT % EFF. MODEL INPUT OUTPUT CAPACITOR NUMBER VOLTAGE VOLTAGE LOAD MAX. MIN. MAX. NO LOAD FULL LOAD (1) (2) CHB150W12-72S05 14-160 VDC 5 VDC 0 mA 25 A 50 mA 1929 mA 90 90 25000uF CHB150W12-72S12 14-160 VDC 12 VDC 0 mA 12.5 A 50 mA 2289 mA 91 90 16700uF CHB150W12-72S15 14-160 VDC 15 VDC 0 mA 10 A 50 mA 2315 mA 90 90 10000uF CHB150W12-72S24 14-160 VDC 24 VDC 0 mA 6.25 A 50 mA 2341 mA 89 89 6250F CHB150W12-72S48 14-160 VDC 48 VDC 0 mA 3.2 A 50 mA 2370 mA 90 89 1500F NOTE: 1. Nominal Input Voltage 72 VDC 2. Measured at Input Voltage 110 VDC 3. An External Input Capacitor 100uF for All Models are Recommended to Reduce Input Ripple Voltage 4. An External Electrolytic Capacitor at least 240uF connected between BUS and -Vin is necessary PART NUMBER Nominal Input Number of Nominal Output Remote On/Off Series Mounting Inserts Voltage Outputs Voltage Logic CHB150W12- II O XX L -Y (Option) 05: 5VDC 12: 12VDC None: M3x0.5 Mounting None: Positive Inserts CHB150W12 72: 72 VDC S: Single 15: 15VDC 24: 24VDC N: Negative -C: Clear Mounting Inserts (3.2mm DIA.) 48: 48VDC Part Number Example: CHB150W12-72S12N-C: Half Brick, 150W, 12:1 14-160Vdc Input, Single 12Vdc Output, Negative Logic, Clear Mounting Insert www.cincon.com 1 REVISION: V10 CHB150W12 Series TECHNICAL SPECIFICATIONS (All specifications are typical at nominal input, full load at 25C unless otherwise noted.) ABSOLUTE MAXIMUM RATINGS PARAMETER NOTES and CONDITIONS Device Min. Typ. Max. Units Input Voltage Continuous -0.3 160 V All dc Input Surge Voltage 100ms max. V All 180 dc Operating Case Temperature At the Center Part of Base Plate C All -40 100 Storage Temperature C All -55 125 INPUT CHARACTERISTICS PARAMETER NOTES and CONDITIONS Device Min. Typ. Max. Units Operating Input Voltage V All 14 72 160 dc Input Under Voltage Lockout Turn-On Voltage Threshold V All 12.5 13 13.5 dc Turn-Off Voltage Threshold V All 10.5 11 11.5 dc Lockout Hysteresis Voltage V All 2 dc Maximum Input Current V =16.5V, Full Load. A in All 12 No-Load Input Current V =72V, Io=0A mA in See Model Number Table Input Filter Pi filter. All 2 2 Inrush Current (I t) As per ETS300 132-2. A s All 0.1 Input Reflected Ripple Current P-P thru 12uH inductor, 5Hz to 20MHz. mA All 50 OUTPUT CHARACTERISTICS PARAMETER NOTES and CONDITIONS Device Min. Typ. Max. Units Voltage Set Point Accuracy V =72V, Full Load, Tc=25C % in All -1.0 +1.0 Output Voltage Regulation Load Regulation Full Load to No Load % All 0.2 Line Regulation V =High Line to Low Line, Full Load % in All 0.2 Temperature Coefficient Tc=-40C to 100C %/C All 0.02 Output Voltage Ripple and Noise (5Hz to 20MHz bandwidth) 5Vo 150 12Vo 200 Peak-to-Peak mV 15Vo 200 24Vo 240 Full load, 10uF tantalum and 1uF ceramic 48Vo 240 capacitors (for Vo=48V: Full Load 10uF 5Vo 60 aluminum and 1uF ceramic capacitors). 12Vo 80 RMS. mV 15Vo 60 24Vo 100 48Vo 100 V = 16.5 to 160V in See Model Number Table Output Current Range A V = 14 to 16.5V in See Model Number Table,Full Load 10S Over Current Protection <90% Vo % All 110 125 140 Short Circuit Protection Hiccup Mode. Auto Recovery. Continuous, Auto Recovery. All External Load Capacitance Full load (Constant resistive load) uF See Model Number Table Pomax rated power, I I Output Voltage Trim Range o o max All % -20 +15 Output Voltage Remote Sense Pomax rated power, I I o o max All % +15 Range % of nominal Vo Over Voltage Protection Limited Voltage, % of Nominal Vo All % 117 125 140 www.cincon.com 2 REVISION: V10