Ordering information Three phase input type(1-stage filter) TAC -10 -683 -O TAC series(4-30A) 1 2 3 4 1 Model Name R 2 Rated Current 3 Line to ground capacitor code:See table 1.1. table1.1 Line to ground capacitor code Line to ground Leakage Current Code capacitor (Input 250/500V 60Hz) (nominal value) 103 0.5mA/1.0mA max 10000pF 223 1.0mA/2.0mA max 22000pF 683 2.5mA/5.0mA max 68000pF 4 Options D :DIN rail installation type The dimensions change when the option is set. * Refer to External view. The terminal cover is retracted inside the unit DIN rail installation type is option Features of TAC series High-attenuation type of common mode noise from 150kHz to 1MHz (1-stage filter) - Three phase rated voltage 500 VAC (voltage range:528V max) - Selectable leakage current value - Push down type terminal block Specifications No. Items TAC-04-683 TAC-06-683 TAC-10-683 TAC-20-683 TAC-30-683 1 Rated Voltage V AC Three Phase 500 (voltage range:528 max) 50/60Hz 2 Rated Current A 4 6 10 20 30 3 Test Voltage (Terminal-Mounting Plate) 2,000 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity 4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MW min at room temperature and humidity 5 Leakage current 250/500V 60Hz 2.5mA/5.0mA max 6 Voltage drop 1.5V max 1.0V max 7 Safety agency approval temperatures -25 to +85C (Refer to Derating Curve) 8 Operating temperature -40 to +85 (Refer to Derating Curve) C 9 Operating humidity 20 to 95%RH (Non condensing) 10 Storage temperature/humidity -40 to +85C/20 to 95%RH (Non condensing) 2 11 Vibration 10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis 2 12 Impact 196.1m/s (20G), 11ms Once each X, Y and Z axis 13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC 14 Case size (without projection) /Weight 63X64X128 mm 2.48X2.52X5.04 inches (WXHXD) /620g max (Option : -D refer to external view) Circuit Diagram Derating Curve Case LINE LOAD 100 1 4 80 2 5 60 40 3 6 20 0 -40 -30 -20 40 50 60 70 80 90 CY Ambient Temperature C CY CY : Line to ground capacitor : Mounting Plate TA-1 Load Factor % TAC,TAH series(4-30A) External view As this product is adopted push-down type terminal block, this appearance is as follows. 1The terminal cover is retracted inside the unit. 2The screws for connecting the terminals are held in the up right position. Standard Type Mounting Plate 128 5.04 (2.5) 50 0.5 118 0.1 1.97 Protection Earth 4.65 Input 20 83.5 Terminal 0.79 3.29 Output Terminal Name Plate Output Input Terminal Terminal Output Terminal 7-M4 Terminal cover 4-f5.5 Terminal cover 0.22 Mounting Hole Closed the terminal cover Tolerance : 1 0.04 Weight : 620g max Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 0.04 Case : PBT Dimensions in mm, =inches Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max DIN rail installation Type (11) 108 10 Mounting Plate (2.5) 50 4.25 0.39 0.43 Input 0.1 1.97 83.5 Terminal 20 3.29 Protection Earth 0.79 Output Terminal Name Plate Output Terminal Input Terminal Output Terminal Terminal cover 7-M4 Terminal cover Closed the terminal cover Tolerance : 1 0.04 Weight : 620g max Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 0.04 Case : PBT Dimensions in mm, =inches Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max DIN rail Note when installing the EMI/EMC Filter on a DIN rail. DIN rail When the EMI/EMC Filter is grounded through Name Plate the DIN rail, the proper noise attenuation may not be achieved. Be sure to connect the protection earth (PE) of the EMI/EMC Filter body to the earth. TA-3 19 19 0.75 (9) 0.75 0.35 (2) 64 2.52 0.08 (2) 7 64 12 0.28 2.52 0.08 0.47 0.5 50 12 1.97 0.47 63 63 2.48 2.48