TRANSFORMERS t transformers SINGLE-PHASE TRANSFORMERS SAFETY FOR SWIMMING-POOL SPOTLIGHTS TR 26 IP20 TECHNICAL DATA TR 26 SAFETY FOR SWIMMING-POOL TRANSFORMER Rated power range: 130, 350 and 700 VA Class I protection against electric shock Single-phase safety transformers intended to supply spotlights in swimming-pools, garden ponds, ornamental Rated primary voltage: 230 V Rated secondary voltage: 12 V fountains and moist locations, where for safety reasons it is necessary to supply with safety extra low voltage (SELV). Thermal class: B(130 C) and F(155 C) It has several taps in the primary winding in order to compensate for the voltage drop in the transformer-spotlight line Maximum ambient temperature (40 C) Frequency: 50/60 Hz conductors and thus gets an adequate brightness in every spotlight. On request we can manufacture transformers Protection index: IP20 with other rated power or voltages, or with other line lengths between transformers and spotlights. Dielectric strenght between primary & secondary: 4,5 kV Dielectric strenght between windings & metallic parts: 2,5 kV POWER REFERENCE DIMENSIONS FOR SPOTLIGHT DISTANCES WEIGHT (VA) (mm) (transformer - spotlight) (kg) A B C D E F G H 130 660130000 84 113 116 101 66 5 7,5 2 1x12V 100W 10-18-25 m 2,00 350 660350000 108 135 138 120 82 6,5 9,5 9,5 1x12V 300W 10-25-40 m 4,45 700 660700000 120 152 166 135 94 7 9,5 2x12V 300W 10-25-40 m 7,89 666600335500000000 DIMENSIONS technical datatechnical datatechnical data STANDARDS PROTECTION IP PROTECTION INDEX IEC 61558-1 IEC 61558-2-6 147 EN 61558-1 172 178-179 EN 61558-2-6t transformers SINGLE-PHASE TRANSFORMERS SAFETY FOR SWIMMING-POOL SPOTLIGHTS TR 26 IP00 TECHNICAL DATA TR 26 SAFETY FOR SWIMMING-POOL TRANSFORMER Rated power range: 130, 350 and 700 VA Class I protection against electric shock Single-phase safety transformers intended to supply spotlights in swimming-pools, garden ponds, ornamental Rated primary voltage: 230 V Rated secondary voltage: 12 V fountains and moist locations, where for safety reasons it is necessary to supply with safety extra low voltage (SELV). It Thermal class: B(130 C) and F(155 C) has several taps in the primary winding in order to compensate for the voltage drop in the transformer-spotlight line Maximum ambient temperature (40 C) Frequency: 50/60 Hz conductors and thus gets an adequate brightness in every spotlight. On request we can manufacture transformers Protection index: IP00 with other rated power or voltages, or with other line lengths between transformers and spotlights. Dielectric strenght between primary & secondary: 4,5 kV Dielectric strenght between windings & metallic parts: 2,5 kV POWER REFERENCE DIMENSIONS FOR SPOTLIGHT DISTANCES WEIGHT (VA) (mm) (transformer - spotlight) (kg) A B C D E F 130 660130001 84 90 90 64 67 4,8 1x12V 100W 10-18-25 m 1,96 350 660350001 108 110 93 90 80 5,0 1x12V 300W 10-25-40 m 3,90 700 660700001 120 135 108 90 117 5,7 2x12V 300W 10-25-40 m 7,80 660350001 DIMENSIONS B C F E D A technical datatechnical datatechnical data STANDARDS PROTECTION IP PROTECTION INDEX IEC 61558-1 IEC 61558-2-6 148 EN 61558-1 172 178-179 EN 61558-2-6 TRANSFORMERS