Bussmann
Square Body DIN 43 653
R
690V (IEC/U.L.) 10-400A
Electrical Characteristics Ordering Information Curves
-TN/80
2 2
I t (A Sec)
Rated -U/80 -/80 Type T Carton
Current Clearing Watts Without Visual Indicator Carton Weight
Size RMS-Amps Pre-arc at 660V Loss Indicator Indicator for Micro Qty. (kg) BIF #
10 3.8 25.5 3.0 170M1308 170M1358 170M1408
16 7.2 48 5.5 170M1309 170M1359 170M1409
20 11.5 78 7 170M1310 170M1360 170M1410
25 19 130 9 170M1311 170M1361 170M1411
32 40 270 10 170M1312 170M1362 170M1412
40 69 460 12 170M1313 170M1363 170M1413
000 50 115 770 15 170M1314 170M1364 170M1414
63 215 1450 16 170M1315 170M1365 170M1415 10 1.34 17056310
80 380 2550 19 170M1316 170M1366 170M1416
100 695 4650 24 170M1317 170M1367 170M1417
125 1200 8500 28 170M1318 170M1368 170M1418
160 2300 16000 32 170M1319 170M1369 170M1419
200 4200 28000 37 170M1320 170M1370 170M1420
250 7750 51500 42 170M1321 170M1371 170M1421
315 12000 80500 52 170M1322 170M1372 170M1422
25 19 130 6 170M2608 170M2658
32 28.5 195 7 170M2609 170M2659
40 50 360 9 170M2610 170M2660
50 95 640 10 170M2611 170M2661
63 170 1200 12 170M2612 170M2662
80 310 2100 15 170M2613 170M2663
100 620 4150 20 170M2614 170M2664
5 1.05 17056312
00 125 1000 6950 25 170M2615 170M2665
160 1900 13000 30 170M2616 170M2666
200 3400 23000 35 170M2617 170M2667
250 6250 42000 45 170M2618 170M2668
315 10000 68500 55 170M2619 170M2669
350 13500 91500 60 170M2620 170M2670
400 18000 125000 70 170M2621 170M2671
U.L. Recognition/CSA Component Acceptance on Size 000. 1 kg = 2.2 lbs. 1 lb = 0.45 kg
n Interrupting rating 200kA (Estimated 300kA) RMS Symmetrical.
n Watts loss provided at rated current.
n Microswitch indicator ordered separately.
Form No.
Page 1 of 2
7-11-01 SB01191 BIF Doc #720013
Bussmann
Square Body DIN 43 653
R
690V (IEC/U.L.) 10-400A
Electrical Characteristics
2
Total Clearing I t Arc Voltage Power Losses
2
The total clearing I t at rated voltage and This curve gives the peak arc voltage, Watts loss at rated current is given in
at power factor of 15% are given in the U , which may appear across the fuse the electrical characteristics. The curve
L
electrical characteristics. For other volt- during its operation as a function of the allows the calculation of the power
2
ages, the clearing I t is found by multi- applied working voltage, E , (RMS) at a losses at load currents lower than the
g
plying by correction factor, K, given as power factor of 15%. rated current. The correction factor, K ,
p
a function of applied working voltage, is given as a function of the RMS load
E , (RMS). current, I , in % of the rated current .
g b
1.5 1.0
1.4
K
p
K U
0.8
L
1.2
1.0
3
10
0.6
9 0.5
8
0.4
7
0.5
0.3
6
0.4
5
0.2
0.3
4
0.2
E I
E
g b
g
3 0.1
200 300 400 500 600 690 30 40 50 60 80 90 100%
100 200 300 400 500 600 690 70
Dimensions
DIN 43 653: Type -U/80, -/80, -TN/80
Size D E F G H K
000 40 21 20 51 8 2
00 51 30 28 67 10 2
Dimension in mm.
1mm = 0.0394 1 = 25.4mm
54
Indicator*
D
K
G
100
78
E H F
*Indication for Size 00 Fuses is a red pin
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Form No.
Page 2 of 2
SB01191 BIF Doc #720013
7-11-01