U Ground Fault L 110395 LR80793 Current Detection Systems OPERATING RANGE: Model BGFL (Relay) Trip currents of 5-60, 30-360, or 100-1200A. Time delay from 0.10 to 1 second. (Adjustable) Trip Currents 5-60,30- 360, or 100 -1200A INPUT POWER: 2 VA plus shunt coil requirements. Rated 120 Vac. INPUT WITHSTAND: 200,000 Amperes RMS for 3 cycles, 50/60 Hz. NOMINAL INPUT VOLTAGE: 120 Volts ac, 125 Volts dc, 24 Volts dc, 48 Volts dc. FREQUENCY: 50/60 Hz. AMBIENT TEMPERATURE RANGE: o o -30 C to +60 C Only for use with GFL sensors. Approximate weight 1.5 lbs. These Class 1 Model BGFL Ground Fault Relays and Sensors are designed to form a system for detecting a ground fault current on a ground ac power system. When a ground fault exceeds a pre-selected Current level and Time Delay setting, the relay initiates a trip signal for a shunt trip disconnect device to open and clear the fault. This BGFL system is designed to provide protection for electrical equipment, not protection for personnel. Meets NEC service entrance equipment standards. Available in three basic styles, Standard, Form C, or Zone Interlocking for coordination of single or multiple ground fault devices in system. Integral test panel with Push To Test and Shunt Trip Bypass pushing for CONTACT RATING ease in proper operational testing of the system, with or without tripping DEVICE the protective device. INRUSH CONT. INPUT POWER Power On LED indicator in cover. Positive visual trip indicator, manual reset. 120 Volts ac 10 A 3 A Infinitely adjustable Time Delay. 125 Volts dc 1 A 1 A Discrete current threshold adjustment. 48 Volts dc 4 A 4 A Panel or door mounting. 24 Volts dc 8 A 8 A Rear terminal kit and clear plastic cover standard with door mounting. Electromechanical relay output, positive ON and OFF. Operates with molded case and power circuit breakers, bolted pressure switches, fusible disconnect switches. HOW TO ORDER RELAYS Internal Circuit Options Aux. Supply Voltage 4=Isolated Internal Form C * 5=120V ac, 50/60Hz 7=With Zone Interlocking 4=125V dc 9=Without Zone Interlocking 3=24V dc 2=48V dc BGFL X X X - XXXX Current Range Mounting 60=5 to 60A 1=Panel mount 360=30 to 360A 1200=100 to 1200A 2=Door mount * Not Available with zone Interlocking option 7 www.GEMultilin.comGround Fault Current Detection Systems Model BGFL (Outlines) USA, Canada, Asia, Latin America Europe, Middle East, Africa Tel: +1-800-547-8629 Tel: +34-94-485-88-00 Fax: +1-905-201-2455 Fax: +34-94-485-88-45 e-mail: sales.multilin ge.com e-mail: gemultilin.euro ge.com 8 Electronic Products Please refer to our website www.GEMultilin.com for more detailed contact information CS00A40768 Rev.2 8/06