Bussmann Industrial HRC Fuse Links BS88, IEC269 AC Centre Bolted Tags 550V ac 250V dc2-32 Amps Time-Current Characteristic Curves Non Motor Rated 16A 20A 25A 32A Centre Bolted Tag 2A 4A 6A 10A Dimensional Data 2 2 It(Amps Seconds) Dimensions (mm) Nom. Catalog Rated Watts Amp Pre- Total at Number Voltage AB C D E F G H K Loss Ratings Arcing 415V AC2 2 1.2 3.1 1.2 AC4 4 11 31 1.4 AC6 6 32 90 1.8 AC10 10 20 60 2.4 550 ac 113.5 97.5 55.5 21.0 1.6 12.7 13.5 7.0 11.2 AC16 16 85 240 2.9 AC20 20 220 580 3.1 AC25 25 500 1400 3.2 AC32 32 1000 2760 3.5 Packaging - 20 per carton This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Bussmann Division Cooper (U.K.) Ltd Head Office Burton-on-the-Wolds St. Louis, MO, U.S.A. Tel: (314) 527-3877 Fax: (800) 544-2570 International Fax: (314) 527-1445 Leicestershire, LE12 5TH United Kingdom Tel: (44) (0)1509 88 27 37 Bussmann Information Fax (00 1) 314 527 1450 Fax: (44) (0)1509 88 27 86 B i F Bussmann WEB site -