Bussmann Stud-Mounted Fuses ACK Dimensional Data All other tolerances ( 0.005) mm ( 0.13) inches A ( 0.031 ) ( 0.79mm) D B F Catalog Symbol: ACK C E Ampere Rating: 10 to 400 Amperes Voltage Rating: 130 Volts DC or less G (10-100): 130 Vdc, (120-200): 72 Vdc, Dimensions in Inches and (mm) (225-300): 48 Vdc Catalog Symbol A B C D E F G Agency Approvals: 2.5 .375 .500 .250 .557 .588 .031 U.L. Recognized (15-300A), Guide JFHR2, File E56412 ACK 1030 (63.5) (9.53) (12.70) (6.35) 14.15) (14.94) (0.79) Electrical Ratings (Catalog Symbol, Amperes and Voltage) 3.0 .470 .685 .344 .812 .860 .051 ACK 3560 ACK-10 130V ACK-40 130V ACK-100 130V ACK-200 72V (76.20) (11.94) (17.40) (8.74) (20.63) (21.84) (1.30) ACK-15 130V ACK-50 130V ACK-120 72V ACK-225 80V 3.5 .547 .750 .312 1.062 1.125 .050 ACK 70100 ACK-20 130V ACK-60 130V ACK-140 72V ACK-250 80V (88.90) (13.89) (19.05) (7.92) (26.98) (28.58) (1.27) ACK-25 130V ACK-70 130V ACK-150 72V ACK-300 80V 3.750 .750 .750 .375 1.062 1.15 .050 ACK 120200 ACK-30 130V ACK-75 130V ACK-160 72V ACK-400 80V (95.25) (19.05) (19.05) (9.52) (26.98) (29.21) (1.27) ACK-35 130V ACK-80 130V ACK-175 72V 3.750 .610 .750 .312 1.062 1.125 .050 ACK 225400 (95.25) (15.49) (19.05) (7.92) (1.062) (28.58) (1.27) Test Specifications Note: 10-60 amp fuses use brass terminals and ferrules. Fuse Load Opening Time 70-400 amp fuses use copper terminals and ferrules. 200% 100 Seconds* ACK 300% 35 Seconds* 500% 13 Seconds* Time-Current CharacteristicsTotal Clear *Approximately. AMPERE RATING General Information: 100 These fuses avoid needless openings from starting currents or surges. A fuse link which operates only on very high overloads or short-circuits. Thermal cutout functions on low overloads the thermal cutout cannot operate quickly at any load, hence long time- 10 lag is obtained on high overloads of short duration. This long time-lag also makes it unnecessary to use extra large size or over-size fuses. Fuseblocks Catalog Block Catalog Block Number Number Number Number 1 ACK 10-30 4228 ACK 120-200 3569 ACK 35-60 3411 ACK 225-400 3578 ACK 70-100 2322 CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document 8002 or contact .1 Bussmann Application Engineering at 314-527-1270 for more information. The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical infor- mation that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications01 CURRENT IN AMPERES Form No. ACK Page 1 of 1 12-17-98 BIF Doc 1040 SB98107 Rev. A TIME IN SECONDS 4 10 10 15 20 30 35 50 100 70 100 150 200 250 300 1,000 2,000X-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for Specialty Fuses category: Click to view products by Eaton manufacturer: Other Similar products are found below : 63NZ02GL 714125 722134 F02A-4AS F02B-1A 80NH00GR-6 FWH-200A FWP-32A14F 12LCT 12TDLSJ63 REN-3 15.5CAVH2E ECF-1 ECF-2 ECF-3 ECF-4 170M0213 170M1369-D 170M3809D BK/F02B-1A N-2-1/2 N-3-2/10 NITD2 20D16 KAA-3 KAB-30 KAW-3 2D16 LKN-125B 16D27SB 16FC 170M1564D 170M2616 170M2668 170M4161 170M4241 170M4699 ESD63 ABS-30 ABS-8 ACF-15 ACF-30 ACO-30 F02A-10A SSD10 200NH1M FWP-25A14FI FWP-40A14FI FWP-500A FWP-63A22FI