Bussmann
Ferrule Type, Fast-Acting Fuses BAN
For 13/32 x 1-1/2 (10.3mm x 38.1mm)
Dimensional Data Time-Current Characteristic CurvesAverage Melt
(Full Size Curves Available)
AMPERE
RATING
100
1.5"
(0.031)
(38.1mm)
0.41"
10
(0.004)
(10.3mm)
Catalog Symbol: BAN
13/32 x 1-1/2 (10.3mm x 38.1mm) 5AG
Ferrule Type, Fast-Acting
1-30A
1
250Vac
Body Material: FIBRE TUBE
Ferrule Material: BRONZE
Ferrule Plating: NICKEL
Interrupting Ratings: Military Tested
35A (1.1 - 3.5A)
100A (3.6 - 10A)
200A (10.1 - 15A)
.1
750A (15.1 - 30A)
Fibre; formerly 5AB.
Mounts in Buss BM series fuseblocks.
Electrical Ratings (Catalog Symbol and Amperes)
250Vac
BAN-1 BAN-5 BAN-10 BAN-25
.01
BAN-2 BAN-6 BAN-12 BAN-30
BAN-3 BAN-7 BAN-15
BAN-4 BAN-8 BAN-20
RMS SYMMETRICAL CURRENT IN AMPERES
Carton Quantity and Weight
Ampere Carton Weight*
Recommended fuseblocks/fuseholders for
Ratings Qty Lbs. Kg.
13/32 x 1-1/2 fuses
1-30 100 1.4 635
See Data Sheets listed below
*Weight per carton.
Open fuseblocks - 1104, 2104
Finger-safe fuseholders - 1109, 1102, 1103, 1151
Panel-mount fuseholders - 2114, 2113, 2108,
2112, 2109, 2140
CE logo denotes compliance with European Union Low Voltage Directive
In-line fuseholders - 2127, 2126
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this Data Sheet are by definition uncontrolled. This bulletin is intended to clear-
ly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any prod-
ucts and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected,
it should be tested by the user in all possible applications.
Form No. BAN
Page 1 of 1
10-2-02 SB02295
Data Sheet: 2046
BAN Fuse Series Discontinued
Effective July 31, 2013
Recommended Replacement is the BAF Series.
See Data Sheet # 2011 for Specifications.
TIME IN SECONDS
1
1
3
10
10
15
20
30
100
1,000