Effective May 2017
Technical Data 2016 Supersedes February 2009
GDC
5 mm x 20 mm Time-delay glass tube fuses
Agency information
cURus Recognition: Guide JDYX2/JDYX8, File
E19180
IMQ Approval: File E1921, CA03.00530
MITI/JET: File JET1641-31003-1005
Ordering
Specify packaging, product, and option code
With TR2 packaging code, lead wire length is 19.05mm
Product features Electrical Characteristics
2.1 I 2.75 I 4 I 10 I
n n n n
Time-delay, low breaking capacity
I max min max min max min max
n
Optional axial leads available
32mA-100mA 2 min 200 ms 10 sec 40 ms 3 sec 10 ms 300 ms
125mA-6.3A 2 min 600 ms 10 sec 150 ms 3 sec 20 ms 300 ms
5 x 20mm physical size
Glass tube, nickel-plated brass endcap
construction
Designed to IEC 60127-2 (32mA-10A)
Specications
Voltage Interrupting Rating (amps) Typical DC Typical Typical
Agency Approvals
2
Product Code Rating at Rated Voltage (50Hz) Cold Resistance Melting I t Voltage
Vac Vac ()* (amps) Drop (mV) cURus IMQ MITI/JET
GDC-32mA 250 35 21.0 0.0051 1050 X X
GDC-40mA 250 35 13.90 0.0072 920 X X
GDC-50mA 250 35 9.24 0.0095 800 X X
GDC-63mA 250 35 6.96 0.021 760 X X
GDC-80mA 250 35 4.42 0.038 580 X X
GDC-100mA 250 35 2.80 0.045 490 X X
GDC-125mA 250 35 1.97 0.063 390 X X
GDC-160mA 250 35 1.27 0.093 320 X X
GDC-200mA 250 35 1.00 0.114 340 X X
GDC-250mA 250 35 0.640 0.265 270 X X
GDC-315mA 250 35 0.450 0.621 250 X X
GDC-400mA 250 35 0.31 0.872 210 X X
GDC-500mA 250 35 0.183 0.827 140 X X
GDC-630mA 250 35 0.186 1.33 150 X X
GDC-800mA 250 35 0.129 2.78 75 X X
GDC-1A 250 35 0.0757 6.45 87.5 X X X
GDC-1.25A 250 35 0.060 10.05 86 X X X
GDC-1.6A 250 35 0.0425 21.7 82 X X X
GDC-2A 250 35 0.03325 31.6 77 X X X
GDC-2.5A 250 35 0.0255 59.4 72.5 X X X
GDC-3.15A 250 35 0.0185 96.4 68.5 X X X
GDC-4A 250 40 0.0139 71.8 67 X X X
GDC-5A 250 50 0.00985 142.5 60.5 X X X
GDC-6.3A 250 63 0.0071 237.6 54 X X X
* DC Cold Resistance (measured at <10% of rated current)
Typical Voltage Drop (voltage drop was measured at 20C ambient temperature at rated current)GDC
Technical Data 2016
Effective May 2017
5 mm x 20 mm Time-delay glass tube fuses
Dimensions - mm
Nominal Time-Current Characterisitics of GDC
Drawing Not to Scale
Packaging Code
Packaging Code Sux Description
BK 100 fuses packed into a cardboard carton
BK1 1,000 fuses packed into a poly bag
TR2 1,500 fuses packed into tape on a reel (19.05mm lead wire length)
Option Code
Option Code Description
V Axial leads - copper tinned wire with nickel plated brass endcaps
Life Support Policy: Eaton does not authorize the use of any of its products for use in life support devices or systems without the express written
approval of an officer of the Company. Life support systems are devices which support or sustain life, and whose failure to perform, when properly
used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in significant injury to the user.
Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also
reserves the right to change or update, without notice, any technical information contained in this bulletin.