Effective May 2017 Technical Data 2016 Supersedes February 2009 GDC 5 mm x 20 mm Time-delay glass tube fuses Agency information cURus Recognition: Guide JDYX2/JDYX8, File E19180 IMQ Approval: File E1921, CA03.00530 MITI/JET: File JET1641-31003-1005 Ordering Specify packaging, product, and option code With TR2 packaging code, lead wire length is 19.05mm Product features Electrical Characteristics 2.1 I 2.75 I 4 I 10 I n n n n Time-delay, low breaking capacity I max min max min max min max n Optional axial leads available 32mA-100mA 2 min 200 ms 10 sec 40 ms 3 sec 10 ms 300 ms 125mA-6.3A 2 min 600 ms 10 sec 150 ms 3 sec 20 ms 300 ms 5 x 20mm physical size Glass tube, nickel-plated brass endcap construction Designed to IEC 60127-2 (32mA-10A) Speci cations Voltage Interrupting Rating (amps) Typical DC Typical Typical Agency Approvals 2 Product Code Rating at Rated Voltage (50Hz) Cold Resistance Melting I t Voltage Vac Vac ()* (amps) Drop (mV) cURus IMQ MITI/JET GDC-32mA 250 35 21.0 0.0051 1050 X X GDC-40mA 250 35 13.90 0.0072 920 X X GDC-50mA 250 35 9.24 0.0095 800 X X GDC-63mA 250 35 6.96 0.021 760 X X GDC-80mA 250 35 4.42 0.038 580 X X GDC-100mA 250 35 2.80 0.045 490 X X GDC-125mA 250 35 1.97 0.063 390 X X GDC-160mA 250 35 1.27 0.093 320 X X GDC-200mA 250 35 1.00 0.114 340 X X GDC-250mA 250 35 0.640 0.265 270 X X GDC-315mA 250 35 0.450 0.621 250 X X GDC-400mA 250 35 0.31 0.872 210 X X GDC-500mA 250 35 0.183 0.827 140 X X GDC-630mA 250 35 0.186 1.33 150 X X GDC-800mA 250 35 0.129 2.78 75 X X GDC-1A 250 35 0.0757 6.45 87.5 X X X GDC-1.25A 250 35 0.060 10.05 86 X X X GDC-1.6A 250 35 0.0425 21.7 82 X X X GDC-2A 250 35 0.03325 31.6 77 X X X GDC-2.5A 250 35 0.0255 59.4 72.5 X X X GDC-3.15A 250 35 0.0185 96.4 68.5 X X X GDC-4A 250 40 0.0139 71.8 67 X X X GDC-5A 250 50 0.00985 142.5 60.5 X X X GDC-6.3A 250 63 0.0071 237.6 54 X X X * DC Cold Resistance (measured at <10% of rated current) Typical Voltage Drop (voltage drop was measured at 20C ambient temperature at rated current)GDC Technical Data 2016 Effective May 2017 5 mm x 20 mm Time-delay glass tube fuses Dimensions - mm Nominal Time-Current Characterisitics of GDC Drawing Not to Scale Packaging Code Packaging Code Su x Description BK 100 fuses packed into a cardboard carton BK1 1,000 fuses packed into a poly bag TR2 1,500 fuses packed into tape on a reel (19.05mm lead wire length) Option Code Option Code Description V Axial leads - copper tinned wire with nickel plated brass endcaps Life Support Policy: Eaton does not authorize the use of any of its products for use in life support devices or systems without the express written approval of an officer of the Company. Life support systems are devices which support or sustain life, and whose failure to perform, when properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in significant injury to the user. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Eaton Electronics Division 1000 Eaton Boulevard Cleveland, OH 44122 United States www.eaton.com/electronics 2017 Eaton Eaton is a registered trademark. All Rights Reserved Printed in USA All other trademarks are property Publication No. 2016 BU-SB08382 of their respective owners. May 2017