Speedstarters,three-phasepowersupplyconnection,three-phasemotor connectionat400V,2,1Aand0,75kW/1HP Partno. DE1-342D1FN-N20N Articleno. 174334 CatalogNo. DE1-342D1FN-N20N Deliveryprogramme Product range PowerXL DE1 Speed Starters Rated operational voltage U 400 V AC, 3-phase e Output voltage with V<sub>e</sub> U 400 V AC, 3-phase 2 Mains voltage (50/60Hz) U V 380 (-10%) - 480 (+10%) LN Ratedoperationalcurrent At 150% overload I A 2.1 e Note Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50C Note Overload cycle for 60 s every 600 s Assignedmotorrating Note for normal internally and externally ventilated 4 pole, three-phase asynchronous -1 -1 motors with 1500 rpm at 50 Hz or 1800 min at 60 Hz Note Overload cycle for 60 s every 600 s Note at 400 V, 50 Hz 150 % Overload P kW 0.75 150 % Overload I A 1.9 e Note at 440 - 480 V, 60 Hz 150 % Overload P HP 1 150 % Overload I A 2.1 e Degree of Protection IP20/NEMA 0 Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU Fitted with Radio interference suppression filter Frame size FS1 Connection to SmartWire-DT with SmartWire-DT module DX-NET-SWD3 Technicaldata General Standards Specification for general requirements: IEC/EN 61800-2 EMC requirements: IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5-1 Certifications CE, UL, cUL, c-Tick Production quality RoHS, ISO 9001 Climatic proofing % < 95%, average relative humidity (RH), non-condensing, non-corrosive (EN50178) w Ambient temperature C operation (150 % overload) C -10 - +50 (max. +60 bis f = 16 kHz without derating) PWM Storage C -40 - +70 Radio interference level Radio interference class (EMC) C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Environment (EMC) 1st and 2nd environments maximum motor cable length I m C2 10 m C3 25 m Mechanical shock resistance g 15 (11 m/s, EN 60068-2-27) Vibration EN 61800-5-1 05/06/2015 174334 - HPL-ED2015 V12.0 EN 1 / 5Altitude m 0 - 1000 m above sea level above 1000m with 1 % performance reduction per 100m max. 2000 m Degree of Protection IP20/NEMA 0 Protection against direct contact BGV A3 (VBG4, finger- and back-of-hand proof) Maincircuit Supply Rated operational voltage U 400 V AC, 3-phase e Mains voltage (50/60Hz) U V 380 (-10%) - 480 (+10%) LN Input current (150% overload) I A 3.1 LN Supply frequency f Hz 50/60 LN Frequency range f Hz 45 - 66 LN Mains switch-on frequency Maximum of one time every 30 seconds Power section Overload current (150% overload) I A 3.15 L max. starting current (High Overload) I % 200 H Note about max. starting current for 1.875 seconds every 600 seconds Output voltage with V U 400 V AC, 3-phase e 2 Output Frequency f Hz 0 - 50/60 (max. 300) 2 Switching frequency f kHz 16 PWM adjustable 4 - 32 (audible) Operation Mode U/f control Speed control with slip compensation Frequency resolution (setpoint value) f Hz 0.025 Rated operational current At 150% overload I A 2.1 e Note Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50C Maximum leakage current to ground (PE) without motor I mA < 3,5 AC, < 10 DC PE Fitted with Radio interference suppression filter Frame size FS1 Motor feeder Note for normal internally and externally ventilated 4 pole, three-phase asynchronous -1 -1 motors with 1500 rpm at 50 Hz or 1800 min at 60 Hz Note Overload cycle for 60 s every 600 s Note at 400 V, 50 Hz 150 % Overload P kW 0.75 Note at 440 - 480 V, 60 Hz 150 % Overload P HP 1 Apparent power Apparent power at rated operation 400 V S kVA 1.45 Apparent power at rated operation 480 V S kVA 1.75 Braking function Standard braking torque max. 30 % M N DC braking torque 100 %, adjustable Controlsection Reference voltage U V 10 V DC (max. 0.2 mA) s Analog inputs 1, parameterizable, 0 - 10 V DC, 0/4 - 20 mA Digital inputs 4, parameterizable, 10 - 30 V DC Relay outputs 1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1) Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU Assignedswitchingandprotectiveelements Power Wiring Safety device (fuse or miniature circuit-breaker) IEC (Typ B, gG) FAZ-B6/3 UL (Class CC or J) A 6 Mains contactor 05/06/2015 174334 - HPL-ED2015 V12.0 EN 2 / 5