Contactor,4kW/400V,ACoperated Partno. DILEM-10(24V50HZ) Articleno. 010005 CatalogNo. XTMC9A10U Deliveryprogramme Product range Contactors Application Mini Contactors for Motors and Resistive Loads Subrange DILEM contactors Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Squirrel-cage motors: starting, switching off during running AC-4: Squirrel-cage motors: starting, plugging, reversing, inching Connection technique Screw terminals Description With auxiliary contact Pole 3 pole Rated operational current AC-3 380 V 400 V I A 9 e AC-1 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 C I =I A 22 th e enclosed I A 16 th Conventional free air thermal current, 1 pole open I A 50 th enclosed I A 40 th Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V P kW 2.2 380 V 400 V P kW 4 660 V 690 V P kW 4 AC-4 220 V 230 V P kW 1.5 380 V 400 V P kW 3 660 V 690 V P kW 3 Contacts N/O = Normally open 1 N/O Contact sequence For use with DILEM DILE Actuating voltage 24 V 50 Hz Voltage AC/DC AC operation Approvals Product Standards IEC/EN 60947-4-1 UL 508 CSA-C22.2 No. 14-05 CE marking UL File No. E29096 UL Category Control No. NLDX CSA File No. 012528 CSA Class No. 3211-04 North America Certification UL listed, CSA certified Specially designed for North America No General Standards IEC/EN 60947, VDE 0660, CSA, UL Lifespan, mechanical Coil 50/60 Hz Operations x 7 6 10 12/04/2013 HPL-ED2013 V2.10 EN 1 / 11Lifespan, mechanical Operations x 10 6 10 Maximum operating frequency Ops./ h Mechanical Ops./ 9000 h Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature C Open C - 25 - 50 Enclosed C - 25 - 40 Mounting position As required except vertical with terminals A1/A2 at the bottom Mounting position As required, except vertical with terminals A1/A2 at the bottom Mechanical shock resistance (IEC/EN 60068-2-27) Half-sinusoidal shock, 10 ms Basic unit without auxiliary contact module Main contacts, make contacts g 10 Main contacts Make/break contacts g 10 / 8 Basic unit with auxiliary contact module Main contacts make contact g Make g 10 Auxiliary contacts Make/break contacts g 20 / 20 Protection type IP20 Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof Weight kg 0.2 Terminal capacity of auxiliary and main contacts 2 Solid 1 x (0.75 - 2.5) mm 2 x (0.75 - 2.5) 2 Flexible with ferrule 1 x (0.75 - 1.5) mm 2 x (0.75 - 1.5) Solid or stranded AWG 18 - 14 Terminal screw M3.5 Pozidriv screwdriver Size 2 Standard screwdriver mm 0.8 x 5.5 1 x 6 Max. tightening torque Nm 1.2 Terminal capacity springloaded terminals main and control circuits 2 Solid 1 x (1 - 2.5) mm 2 x (1 - 2.5) 2 Flexible with ferrule 1 x (1 - 2.5) mm 2 x (1 - 2.5) Standard screwdriver mm 0.6 x 3.5 Mainconductingpaths Rated impulse withstand voltage U V 6000 imp AC Overvoltage category/pollution degree III/3 Rated insulation voltage U V 690 i AC Rated operational voltage U V 690 e AC Safe isolation to EN 61140 between coil and contacts V 300 AC between the contacts V 300 AC Making capacity (cos to IEC/EN 60947) A 110 Breaking capacity 220 V 230 V A 90 380 V 400 V AC A 90 500 V A 64 12/04/2013 HPL-ED2013 V2.10 EN 2 / 11