Contactor,3p+2N/O+2N/C,110kW/400V/AC3 Partno. DILM225A/22(RAC240) Articleno. 139547 CatalogNo. XTCE225H22B Deliveryprogramme Product range Contactors Application Contactors for Motors Subrange Standard devices greater than 170 A Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Squirrel-cage motors: starting, switching off during running AC-4: Squirrel-cage motors: starting, plugging, reversing, inching Connection technique Screw connection Rated operational current AC-3 380 V 400 V I A 225 e AC-1 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 C I =I A 386 th e enclosed I A 275 th Conventional free air thermal current, 1 pole open I A 707 th enclosed I A 636 th Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V P kW 70 380 V 400 V P kW 110 660 V 690 V P kW 150 1000 V P kW 108 AC-4 220 V 230 V P kW 51 380 V 400 V P kW 90 660 V 690 V P kW 110 1000 V P kW 77 Contact sequence Can be combined with auxiliary contact DILM1000-XHI Actuating voltage RAC 240: 190 - 240 V 50/60 Hz Voltage AC/DC AC operation Contacts N/O = Normally open 2 N/O N/C = Normally closed 2 NC Auxiliary contacts possible variants at auxiliary contact module fitting options on the side: 2 x DILM1000-XHI(V)11-SI 2 x DILM1000-XHI11-SA Side mounting auxiliary contacts Instructions integrated suppressor circuit in actuating electronics 660 V, 690 V or 1000 V: not directly reversing Approvals Product Standards IEC/EN 60947-4-1 UL508 CSA-C22.2 No.14-05 CE marking UL File No. E29096 04/17/2014 HPL-ED2014 V2.14 EN 1 / 11UL Category Control No. NLDX CSA File No. 2389068 CSA Class No. 3211-04 North America Certification UL listed, CSA certified Specially designed for North America No General Standards IEC/EN 60947, VDE 0660, UL, CSA Lifespan, mechanical AC operated Operations x 10 6 10 DC operated Operations x 10 6 10 Operating frequency, mechanical AC operated Operations/ 3000 h DC operated Operations/ 3000 h Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature C Open C - 40 - + 60 Enclosed C - 40 - + 40 Storage C - 40 - + 80 Mounting position Mechanical shock resistance (IEC/EN 60068-2-27) Half-sinusoidal shock, 10 ms Main contacts N/O contact g 10 Auxiliary contacts N/O contact g 10 N/C contact g 8 Protection type IP00 Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof with terminal shroud or terminal block Weight AC operated kg 3.54 DC operated kg 3.54 Weight kg 3.54 Terminal capacity main cable Flexible with cable lug 2 50 - 185 mm Stranded with cable lug 2 70 - 185 mm Solid or stranded AWG 2/0 - 250 MCM Flat conductor Lamellenzahl mm Fixing with flat cable terminal or cable terminal blocks x Breite x See terminal capacity for cable terminal blocks Dicke Busbar Breite mm 32 Main cable connection screw/bolt M10 Tightening torque Nm 24 Terminal capacity control circuit cables Solid 2 1 x (0.75 - 2.5) mm 2 x (0.75 - 2.5) 2 Flexible with ferrule 1 x (0.75 - 2.5) mm 2 x (0.75 - 2.5) Solid or stranded AWG 2 x (18 - 12) Control circuit cable connection screw/bolt M3.5 Tightening torque Nm 1.2 04/17/2014 HPL-ED2014 V2.14 EN 2 / 11