Palmswitch,2N/C,emergencyswitchingoff,surfacemounting Partno. FAK-R/V/KC02/IY Articleno. 256790 CatalogNo. FAK-R-V-KC02-IY Deliveryprogramme Product range Foot and palm switches Basic function Basic devices Single unit/Complete unit Complete unit Function maintained Description Pull to release Emergency stop pushbutton tamper-proof to ISO13850/EN418 Contacts N/C = Normally closed 2 NC Notes = safety function, by positive opening to IEC/EN 60947-5-1 Enclosurecolor Colour Enclosure base RAL 9005, black Operator only RAL 1004, yellow yellow Colour Button Red enclosure top Yellow Enclosure base Black Approval Connection to SmartWire-DT no 03/18/2016 256790 - HPL-ED2016 V20.0 EN 1 / 3Technicaldata General 6 Lifespan, mechanical Operations > 0.1 x 10 Operating frequency Operations/h 600 Actuating force N 40 - 60 Degree of protection, IEC/EN 60529 IP67, IP69K Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Open C -25 - +40 Mounting position As required Mechanical shock resistance g > 15 Shock duration 11 ms Sinusoidal according to IEC 60068-2-27 DesignverificationasperIEC/EN61439 Technical data for design verification Rated operational current for specified heat dissipation I A 6 n Heat dissipation per pole, current-dependent P W 0.11 vid Equipment heat dissipation, current-dependent P W 0 vid Static heat dissipation, non-current-dependent P W 0 vs Heat dissipation capacity P W 0 diss Operating ambient temperature min. C -25 Operating ambient temperature max. C 40 IEC/EN 61439 design verification 10.2 Strength of materials and parts 10.2.2 Corrosion resistance Meets the product standard s requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard s requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard s requirements. 10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard s requirements. and fire due to internal electric effects 10.2.4 Resistance to ultra-violet (UV) radiation Please enquire 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard s requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard s requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder s responsibility. 10.8 Connections for external conductors Is the panel builder s responsibility. 10.9 Insulation properties 10.9.2 Power-frequency electric strength Is the panel builder s responsibility. 10.9.3 Impulse withstand voltage Is the panel builder s responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder s responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder s responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder s responsibility. The specifications for the switchgear must be observed. 10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. TechnicaldataETIM6.0 Low-voltage industrial components (EG000017) / Foot-/palm switch complete (EC000231) Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Foot, palm switch (ecl ss8.1-27-37-12-17 AKF035011 ) 03/18/2016 256790 - HPL-ED2016 V20.0 EN 2 / 3