BUSSMANN Effective December 2015 Technical Data 2029 Supersedes April 2014 SERIES FNA 1332 x 1-12 250Vac pin indicating time-delay supplemental fuses Catalog symbol / color code: Features: FNA Color coded by maximum voltage rating Green (250Vac max, 1/10 to 6A) Pin indication for visual indication of open Blue (125Vac max, 6-1/4 to 15A) fuse condition Grey (32Vac max, 20 to 30A) Dual-element, time-delay performance Description: permits close sizing on control transformers and relays Pin indicating, time-delay supplemental fuse. Silver-plated pin for positive, electrical signal Specifications: activation Ratings 12 amp and more versions are dual-tube 250Vac 125Vac construction 1/10 6-1/4 Interrupting rating at Agency system voltage information to to Fuse Typical applications 6A 10A amp 250 125 32 Power electronic circuits with high inrush range Vac Vac Vac UL CSA currents and fuse openings must be quickly 1/10 to 35A 10kA X X apparent 8/10 Inductive load circuits where pin indication 1 to 6 200A 10kA X X of open fuse condition is desired 6-1/4 to 15 10kA X X 20 to 30 1kA Recommended fuse blocks/fuse holders Agency information Catalog symbol Description Data sheet CE symbol Blocks No. UL Listed 1/10 to 8/10A 125/250Vac, 1-, 2- and 3-pole 1-15A 125Vac, Guide JDYX, File E19180 BMM modular blocks with 10235 optional covers CSA Certified 1/10 to 10A 125Vac, 125Vac 3839 4-pole signaling block * Class 1422-01, File 53787 12 to 15A Panel mount holders HPF-C 1-pole holder** 2114 Catalog numbers (amps) Fuseclips FNA-1/10 FNA-1 FNA-3 FNA-9 1A3400, 5956 PCB fuseclips 2132 FNA-1/8 FNA-1-1/8 FNA-3-2/10 FNA-10 and 5960 FNA-15/100 FNA-1-1/4 FNA-3-1/2 FNA-12 * Call toll-free 855-287-7626 (855-BUSSMANN) Eatons Bussmann Division application engineering for FNA-2/10 FNA-1-4/10 FNA-4 FNA-15 details. FNA-1/4 FNA-1-1/2 FNA-4-1/2 FNA-20 ** 1/10 to 10A single tube fuses only. FNA-3/10 FNA-1-6/10 FNA-5 FNA-25 FNA-4/10 FNA-1-8/10 FNA-5-6/10 FNA-30 FNA-1/2 FNA-2 FNA-6 Dimensions - in: FNA-6/10 FNA-2-1/4 FNA-6-1/4 32Vac 0.406 FNA-3/4 FNA-2-1/2 FNA-7 (0.004) 20 to 30A FNA-8/10 FNA-2-8/10 FNA-8 Carton quantity 0.406 0.817 Amps Qty. 0.406 1/10 to 30 10 1.5 0.063 0.343 (blown)FNA Technical Data 2029 250Vac pin indicating time-delay supplemental fuses Effective December 2015 Time-current characteristic curves average melt: Amp rating Amp Rating 100 10 1 0.1 0.01 Current in amps Current in Amps The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton 1000 Eaton Boulevard For Eatons Bussmann series Cleveland, OH 44122 product information, United States Eaton.com call 1-855-287-7626 or visit: Bussmann Division Eaton.com/bussmannseries 114 Old State Road Eaton and Bussmann are valuable Ellisville, MO 63021 trademarks of Eaton in the US and other United States countries. You are not permitted to use the Eaton.com/bussmannseries Eaton trademarks without prior written consent of Eaton. 2015 Eaton Follow us on social media to get the All Rights Reserved CSA is a registered trademark of the latest product and support information. Printed in USA Canadian Standards Group. Publication No. 2029 BU-SB14292 UL is a registered trademark of the December 2015 Underwriters Laboratories, Inc. Time in seconds Time in Seconds 1 10 15 20 100 1000