TRON In-Line Fuse Holders 13 1 HEB Series Single-Pole Breakaway & Non-Breakway for 32 x 1 2 Fuses Specification Data - Non-Breakaway & Loadside Breakaway Conductor Terminals Conductor Data Catalog Terminal Type Size Symbol Load & Line (2) & (3) Copper Crimp 12 to 8 1 A Non-Breakaway Fuse Holders 12 2 See page 2 for breakaway holders 10 2 B 6 1 Catalog Symbol: HEB 8 2 C Description: 4 1 Water resistant, single-pole non-breakaway in-line fuse holders 6 2 D 13 1 2 1 for 32 x 1 2 midget fuses. Typical fuse types: BAF, DCM, 4 2 E FNM, FNQ and KTK. 20 to 18 1 Z Ratings: Copper Setscrew Volts: 600V (or less) Amps: Up to 30A* 12 to 3 1 J Agency Information: (1) UL Recognized, Guide IZLT2, File E14853 (2) CSA Certified, Class 6225-01, File 47235 12 to 3 2 K (3) CE Coupling Nut Torque: 10-20lb-in. Solid Copper Terminal for Part Number Explanation Aluminum Wire Connector Example: HEB-AK 8 to 12 11 S HEB = Holder series 10 to 4 11 A = Loadside terminal (copper crimp for 12 solid copper wire) Aluminum Crimp 8 1 N K = Lineside terminal (copper setscrew for two 6 solid 6 1 6 1 copper wires) P 4 1 Part Number Selection 3, 4 1 Q From the table on page three, select the combination of 2 1 1, 2 1 R desired loadside and lineside terminals for the application 1/0 1 T (define terminal type, wire size, number of wires per terminal and whether the terminal accepts solid and/or stranded Aluminum Setscrew conductors). Then in the right hand two columns, select either the non-breakaway or breakaway holder part number to order. 12 to 2 1 L Available Part Numbers (1) (2) (3) (2) (2) HEB-AA , HEB-AB , HEB-AC , (2) (2) HEB-AD , HEB-AE , HEB-AJ, HEB-AK, HEB-AL, HEB-AR, 12 to 2 2 Y (2) (2) (2) (2) HEB-AY, HEB-BA , HEB-BB , HEB-BC , HEB-BD , (2) (2) HEB-CC , HEB-DD , HEB-JJ, HEB-JK, HEB-JL, HEB-JY, (2) (2) (2) HEB-LL, HEB-NN, HEB-PP , HEB-QQ , HEB-RR , (2) HEB-SS, HEB-TT , HEB-ZA. Insulating Boots For insulating boots, see page 2. Insulating boots are not included with non-breakaway holders and must be ordered separately. They come standard with the breakaway holders. When insulating boots are utilized, extra heat retention requires that fuses are sized at a minimum of 200% of the RMS load current. *Amp rating limited by conductor size. 0908 BU-SB08489 Page 1 of 3 Data Sheet 2127 No. Per Terminal Solid StrandedBreakaway Fuse Holders Specification Data - Lineside Breakaway Catalog Symbol: HEB Breakaway Receptacles Description: Conductor Data Catalog 13 1 Single-pole breakaway in-line fuse holders for 32 x 1 2 Terminal Type Size Symbol midget fuses. Typical fuse types: BAF, DCM, FNM, FNQ AND KTK. Ratings: Copper Crimp 12 to 8 1 -RLC-A Volts: 600V (or less) 6 1 -RLC-B Amps: Up to 30A* 4 1 -RLC-C Copper Setscrew Agency Information: (1) UL Recognized, Guide IZLT2, File E14853 (2) 12 to 2 1 -RLC-J CSA Certified, Class 6225-01, File 47235 (3) CE Coupling Nut Torque: 10-20lb-in. Part Number Explanation 12 to 2 2 -RYC Example: HEB-AW-RYC HEB = Holder series Aluminum Setscrew AW = Loadside terminal (copper crimp for 12 solid copper wire) 12 to 2 1 -RLA RYC = Lineside terminal (copper setscrew for two 6 solid copper wires) Part Number Selection 12 to 2 2 -RYA From the table on page three, select the combination of desired loadside and lineside terminals for the application (define terminal type, wire size, number of wires per terminal and whether the Solid Breakaway (Required with W Breakaway terminal accepts solid and/or stranded conductors). Then in the Receptacle) right hand two columns, select either the non-breakaway or breakaway holder part number to order. Available Part Numbers Breakaway Units: (Includes fuse holder, breakaway part and insulating boots): Insulating Boots (1) (2) (3) HEB-AW-RLA, HEB-AW-RLC-A , HEB-AW-RLC-B, Part Numbers Type HEB-AW-RLC-C, HEB-AW-RLC-J, HEB-AW-RYA, 2A0660 Single conductor HEB-AW-RYC, HEB-BW-RLC-A, HEB-BW-RLC-B, 2A0661 Two conductor HEB-BW-RYC, HEB-JW-RLC-J, HEB-JW-RYC, HEB-KW-RLC-J, HEB-KW-RYC, HEB-LW-RLA, Two insulating boots come standard with the breakaway holders HEB-LW-RLC-J, HEB-LW-RYA (2) (2) (2) (example: HEB-AW-RLC-A). The insulating boots are not Fuse Holder Only: HEB-AW , HEB-BW , HEB-DW , included with the non-breakaway holders (example: HEB-AA) or HEB-JW, HEB-LW the individual pieces of the breakaway holders (example: Breakaway Part: RLC-A, RLC-B, RLC-C, RLC-J, HEB-AW, RCL-A). Two insulating boots must be ordered for RYC, RLA, RYA each holder when ordering them separately. When insulating boots are utilized, extra heat retention requires that fuses are sized at a minimum of 200% of the RMS load current. *Amp rating limited by conductor size. 0908 BU-SB08489 Page 2 of 3 Data Sheet 2127 No. Per Terminal Solid Stranded