F E S U F Bussmann Panel-Mount Fuseholder HPG and HPD Dimensional Data With Fuse HPG 2.81 Max. (71.4mm) HPG-EE 0.88 (22.2mm) 1.125 .250 .003 (28.6mm) (6.35 .08mm) (Typ. 2) HPD Catalog Symbol: HPG and HPD Panel-Mount Agency Information: UL Recognized, Guide IZLT2, File E14853 Flammability Rating: UL 94VO-Fuseholder Body UL94HB-Knob General Information: Bayonet-type knob. For supplementary protection of transformers, relays, ballasts and small motors. Mount in (12.7mm) knock-outs with locknut. Do not put tension on line (ear) terminal. Punched Mounting Hole Electrical Ratings + .880 .005 + Catalog Volts (22.4mm .13mm) Symbol Amps AC Fuse Description (3) HPG 30 600 x 1 (10.3 x 38.1mm) + .815 .005 + HPG-EE 15 600 SC 0-15, 1 fuses. (20.7mm .13mm) (3) HPD 30 600 x 1 (10.3 x 38.1mm) (3) 20A max when used with quick connect terminals Maximum panel thickness, mounting flange in front of panel NOTE: Assumes Pollution Degree 3 per UL 840: Conductive pollution, or dry, nonconductive pollution that HPG and HPG-EE has combination quick-connect/solder becomes conductive due to condensation that is expected. terminals on both side (load) and rear (line) terminals. HPD has combination quick-connect/solder terminal on side Maximum panel thickness not including any sealing gaskets. 3 16 (load) terminal only. Rear (line) terminal is / shorter than System Voltage 600V 480 277 240 120 HPG. Rear terminal solder only. Fuseholder mm Inches mm Inches mm Inches mm Inches mm Inches HPG 0.84 1/32 1.73 1/16 6.00 7/32 6.55 1/4 8.03 5/8 HPD 0.84 1/32 1.73 1/16 6.00 7/32 6.55 1/4 8.03 5/8 Thicker panels may be used if fuse holder load terminal is fully insulated, using a UL recognized (VW-1) insulative heat-shrink tubing, or if anticipated environment is of Pollution Degree 1 or 2, or if panel is nonconductive. Pollution Degree 2- Normally, only nonconductive pollution. However, a temporary CE logo denotes compliance with European Union Low Voltage Directive conductivity caused by condensation may be expected. (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Pollution Degree 1- No pollution or only dry, nonconductive pollution. Application Engineering at 636-527-1270 for more information. The pollution has no influence. Maximum panel thickness, mounting flange behind the panel: 5.08mm/0.200 (flush to knob collar) The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information con- tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Form No. HPG Page 1 of 1 SB04184 6-3-04 Data Sheet: 2108 E S U F E S UX-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for Fuse Holder category: Click to view products by Eaton manufacturer: Other Similar products are found below : 570-290-741P40 570-290-751P40 020417G 020418E 6R30A1B F600A3B 80910030 8601.2020 G15A2SPQ 9-3557-GP REV A HDJ-B R6J30A3S HFH-1 RF30A1S RF30A2B RF30A3SP 15600-08-10 BK/FHN19G BK/HHM BK/HKP-CCHH BK/HKP-JJ BK/HTJ-LES- FUSE HMG-241 HTJ-LES-FUSE C4044-1 2086-1 2193 2602 2650 178.000100 FHN31G1 T30A2B G4PB8 2660 2799 CQ-209V HKP- CCHH R6F30A2S 341001A 345621A CVRMCC 4202 4407 4408 4413 4423 4532 4537 TSD1404-12 BK/FHN31G1