Low-Peak Class L KRP-C 600Vac, 2001-6000A, Time-Delay Fuses Dimensions - in 0.88 1.63 1.38 1.38 1.75 1.75 0.81 0.88 6.75 2001A 3500A 4500A to 3000A to to 6000A 3.75 10.75 2500A 4000A 5000A ( 0.09) Description: Ultimate protection Class L current-limiting, 1 0.75 0.75 0.75 1 time-delay fuses. Time-delay 4 seconds (minimum) at 500% of rated current. Catalog Symbol: KRP-C-(amp)SP 3.5 4 4.75 5.25 5.75 5 5 5.75 6.25 7.13 Ratings: 5.03 Max. 5.03 Max. 5.79 Max. 7.17 Max. 7.17 Max. Terminals: Width ( 0.06), Thickness ( 0.03) Volts 600Vac Amps 2001-6000A Features: IR 300kA Vac RMS Sym. Industry s only UL Listed and CSA Certified fuse with a 300kA interrupting rating that allows for simple, worry-free Agency Information: installation in virtually any application. CE, UL Listed, Guide JDDZ, File E4273 Fast short-circuit protection and dual-element, time-delay CSA Certified, Class 1422-02, File 53787, performance provide ultimate protection. Reduces existing fuse inventory by up to 33% when Class L per CSA-C22.2 No. 248.10 upgrading to Low-Peak fuses. RoHS Compliant Consistent 2:1 ampacity ratios for all Low-Peak fuses make Catalog Numbers (amps) selective coordination easy. KRP-C-2001SP KRP-C-3500SP KRP-C-5000SP Time-delay for close sizing load. KRP-C-2400SP KRP-C-3800SP KRP-C-6000SP Current-limiting action of the fuse generally affords KRP-C-2500SP KRP-C-4000SP considerable reduction in bus bracing. KRP-C-3000SP KRP-C-4500SP All-purpose silver-linked fuse for both overload and short- circuit protetion for high capacity systems (mains and large Carton Quantity: feeders). Amp Rating Carton Qty. O-ring seals maximize pressure build-up during current- 2001-6000 1 limiting action and ensure filter retention. High-grade silica sand filler accelerates response of fuse to short-circuits by having quenching effect on the fuse arc. 99.9% Pure silver links provide low watt loss with low operating temperature on normal current levels and I2 minimizes total clearing t fault energy left-through. 0813 BU-SB13XXX Page 1 of 3 Data Sheet 1009Low-Peak Class L KRP-C 600Vac, 2001-6000A, Time-Delay Fuses Time-Current Curves - Average Melt AMP RATING 300 100 10 1 0.1 0.01 CURRENT IN AMPS 0813 BU-SB13XXX Page 2 of 3 Data Sheet 1009 TIME IN SECONDS 1000 2500A 3000A 10,000 4000A 5000A 6000A 100,000 200,000