Effective February 2016 Technical Data 1008 Supersedes August 2015 Low-Peak KRP-C Class L 600Vac/300Vdc, 601-2000A, time-delay fuses Catalog numbers (amps) KRP-C-601SP KRP-C-900SP KRP-C-1500SP KRP-C-650SP KRP-C-1000SP KRP-C-1600SP KRP-C-700SP KRP-C-1100SP KRP-C-1800SP KRP-C-750SP KRP-C-1200SP KRP-C-1900SP KRP-C-800SP KRP-C-1350SP KRP-C-2000SP KRP-C-801SP KRP-C-1400SP Carton quantity: Amp rating Carton qty. 601-2000 1 Dimensions - in: All other tolerances ( 0.02) All Slots and Holes 0.63 (0.03) Catalog symbol: KRP-C-(amp)SP 8.63 ( 0.09) 601 801 1350 1800 6.75 to 5.75 to to to 3.75 Description: 10.75 800A 1200A 1600A 2000A ( 0.09) Bussmann series Ultimate protection KRP-C Class L current-limiting, time-delay fuses. Time- delay 4 seconds (minimum) at 500% of rated 0.5 0.44 0.38 0.38 current. Terminal: Specifications: Width ( 0.06) Thickness ( 0.03) 2.75 2 2 2.38 Ratings 2.5 2.5 3 3.5 2.53 2.78 3.03 3.53 Volts Max. Max. Max. Max. 600Vac Features: 300Vdc Industrys only UL Listed and CSA Certified fuse with a 300kA interrupting rating that allows Amps 601-2000A* for simple, worry-free installation in virtually any IR application. 300kA Vac RMS Sym. Fast short-circuit protection with time-delay performance provide ultimate protection. 100kA Vdc Consistent 2:1 ampacity ratios for all Low-Peak * Use KRP-CL fuses for ratings from 225 to 600 amps. fuses make selective coordination easy. Agency information Time-delay for close sizing load. UL Listed, Guide JDDZ, File E4273 Current-limiting action of the fuse generally affords considerable reduction in bus bracing. CSA Certified, Class 1422-02, File 53787, All-purpose silver-linked fuse for both overload and Class L per CSA C22.2, No. 248.10 short-circuit protetion for high capacity systems CE (mains and large feeders). RoHS compliant O-ring seals maximize pressure build-up during current-limiting action and ensure filter retention. High-grade silica sand filler accelerates response of fuse to short-circuits by having quenching effect on the fuse arc. 99.9% pure silver links provide low watt loss with low operating temperature on normal current 2 levels and minimizes total clearing I t fault energy left-through.Low-Peak KRP-C Class L 600Vac/300Vdc, Technical Data 1008 601-2000A, time-delay fuses Effective February 2016 Recommended fuse blocks 601 to 1200 amps Time-current curves - average melt Catalog numbers Poles 51215 1 51235 3 AMP RATING 300 No Agency listings available. No reducers available. 100 10 1 0.1 0.01 CURRENT IN AMPS 2 Eaton.com/bussmannseries TIME IN SECONDS 1000 800A 1200A 1600A 2000A 10,000 100,000 200,000