Type: P125/I2 Article No.: 207299 Ordering information Design Surface mounting Description Without auxiliary contacts Main conducting paths No. of poles M 3 Auxiliary contacts N/O 0 Auxiliary contacts B 0 Max. threephase motor rating (per set of 3 contacts) 5060 Hz AC3 400/415 P kW 13 V 5060 Hz Rated uninterrupted current I A 25 u Contact sequence General IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA,UL Standards Switchdisconnectors to IEC/EN 609473 6 Lifespan, mechanical Operations 10 0,3 Maximum operating frequency Operations/h 50 1Damp heat, constant, to IEC Climatic proofing 60068278 Damp heat, cyclical, to IEC 60068230 Ambient temperature Open C 25/50 Enclosed C 25/40 Mounting position As required Documentation Main catalogue HPL Mechanical shock resistance g > 15 (shock duration 20 ms) Contacts Rated operational voltage U V AC 690 e Rated impulse withstand voltage U V AC 6000 imp Overvoltage category/pollution III/3 degree Rated uninterrupted current open I A 25 u Enclosed I A 25 u Loadcarrying capacity in intermittent operation, Class 12 AB 25 % DF I 2 e AB 40 % DF I 1,6 e AB 60 % DF I 1,3 e Shortcircuit rating Fuse A gG/gL 25 Rated shorttime withstand I A 640 cw rms current (1 s current) Switching angles 90 Current heat loss per contact at I W 1,1 e Terminal capacities 1 (1.5 6) 2 Solid or stranded mm 2 (1.5 6) 1 (1 4) 2 Flexible with ferrule to DIN 46228 mm 2 (1 4) Terminal screw M4 Tightening torque Nm 1.6 Switching capacity AC Rated making capacity cos = 0.35 A 240 Rated breaking capacity, motor load switch cos = 0.35 2