Type: P3100/I5/SVB Article No.: 207373 Ordering information Design Surface mounting Description Without auxiliary contacts Main conducting paths No. of poles M 3 Auxiliary contacts N/O 0 Auxiliary contacts B 0 Max. threephase motor rating (per set of 3 contacts) 5060 Hz AC3 400/415 P kW 50 V 5060 Hz Rated uninterrupted current I A 100 u According to IEC/EN 602041, VDE 0113 Part 1 with red Note for table header rotary handle and yellow locking collar, lockable in 0 position Contact sequence General IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA,UL Standards Switchdisconnectors to IEC/EN 609473 6 Lifespan, mechanical Operations 10 0,1 1Maximum operating frequency Operations/h 50 Damp heat, constant, to IEC Climatic proofing 60068278 Damp heat, cyclical, to IEC 60068230 Ambient temperature Open C 25/50 Enclosed C 25/40 Mounting position As required Documentation Main catalogue HPL Mechanical shock resistance g > 15 (shock duration 20 ms) Contacts Rated operational voltage U V AC 690 e Rated impulse withstand voltage U V AC 6000 imp Overvoltage category/pollution III/3 degree Rated uninterrupted current open I A 100 u Enclosed I A 100 u Loadcarrying capacity in intermittent operation, Class 12 AB 25 % DF I 2 e AB 40 % DF I 1,6 e AB 60 % DF I 1,3 e Shortcircuit rating Fuse A gG/gL 100 Rated shorttime withstand I A 2000 cw rms current (1 s current) Switching angles 90 Current heat loss per contact at I W 7,5 e Terminal capacities 1 (2.5 35) 2 Solid or stranded mm 2 (2.5 10) 1 (1.5 25) 2 Flexible with ferrule to DIN 46228 mm 2 (1.5 6) Terminal screw M5 Tightening torque Nm 3 Switching capacity AC Rated making capacity cos = 0.35 A 950 2