PKE12+tripbloc kStandard0.3-1.2A Partno. PKE12/XTU-1,2 Articleno. 121731 Deliveryprogramme Single unit/Complete unit Complete unit Setting range of overload releases I A 0.3 - 1.2 r Function With overload release Motor rating AC-3 220 V 230 V P kW 0.18 380 V 400 V P kW 0.37 660 V 690 V P kW 0.75 Motor AC-3 power rated motor current 220, 230 380, 400, 440 V 500 V 660, 690 V 240 V 415 V P kW I A) I A) I A) I A) I A) 0.06 0.37 0.09 0.54 0.31 0.12 0.72 0.41 0.37 0.33 0.18 1.04 0.6 0.54 0.48 0.35 0.25 0.8 0.76 0.7 0.5 0.37 1.1 1.02 0.9 0.7 0.55 0.9 0.75 1.1 Approvals Product Standards UL508 CSA-C22.2 No.14-10 IEC60947-4-1 CE marking UL File No. E36332 UL CCN NLRV CSA File No. 12528 CSA Class No. 3211-05 NA Certification UL listed, CSA certified Specially designed for NA No General Standards IEC/EN 60947, VDE 0660 Climatic proofing Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 Ambient temperature C Storage C -40 - +80 Open C -20 - +55 Enclosed C -20 - +40 Mounting position Direction of incoming supply as required Degree of protection Device IP20 Terminations IP00 EN50274 busbar tag shroud Finger and back-of-hand proof Mechanical shock resistance half-sinusoidal shock 10 ms to IEC g 25 60068-2-27 Altitude m 2000 2 Terminal capacity screw terminals mm 2 Solid 1 x (1 - 6) mm 2 x (1 - 6) Flexible with ferrule to DIN 46228 2 1 x (1 - 6) mm 2 x (1 - 6) 06/25/2012 HPL-ED2012 V1.1 EN 1 / 4Solid or stranded AWG 18 - 10 Specified tightening torque for terminal screws Main cable Nm 1.7 Control circuit cables Nm 1 Mainconductingpaths Rated impulse withstand voltage U V 6000 imp AC Overvoltage category/pollution degree III/3 Rated operational voltage U V 690 e AC Rated uninterrupted current = rated operational current I = I A 1.2 u e Rated frequency f Hz 40 - 60 Current heat loss (3 pole at operating temperature) W 0.4 Lifespan, mechanical Operations x 0.05 6 10 Lifespan, electrical (AC-3 at 400 V) Operations x 0.05 6 10 Maximum operating frequency Ops./ h Max. operating frequency Ops/ 60 h Motor switching capacity kA rms AC-3 (up to 690 V) A 1 Tripbloc k s Temperature compensation C -5 40 (to IEC/EN 60947, VDE 0660) -25 55 (operating range) Temperature compensation residual error for T > 40 C 0.1%/K Setting range of overload releases 0.25 - 1 x I u Fixed short-circuit release Basic device 14 x I u Trip block 12 x I r delayed approx. 60 ms Short-circuit release tolerance 20% Phase-failure sensitivity yes Tec hnic aldataETIM4.0 Rated operation power at AC-3, 400 V kWh 0.25 With integrated auxiliary switch No Rated permanent current Iu A 1.2 With integrated under voltage release No Number of poles 3 Degree of protection (IP) IP20 Connection type main current circuit Screw connection Characteristic s 06/25/2012 HPL-ED2012 V1.1 EN 2 / 4