Type: T5415682/I5/SVB Article No.: 207281 Ordering information Design Surface mounting Description With auxiliary contacts Main conducting paths No. of poles M 6 Auxiliary contacts N/O 1 Auxiliary contacts B 1 Max. threephase motor rating (per set of 3 contacts) 5060 Hz AC3 400/415 P kW 30 V 5060 Hz Rated uninterrupted current I A 100 u According to IEC/EN 602041, VDE 0113 Part 1 with red Note for table header rotary handle and yellow locking collar, lockable in 0 position Contact sequence General Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL Switchdisconnectors to IEC/EN 609473 Loadbreak switches to 1IEC/EN 609473 6 Lifespan, mechanical Operations 10 0,5 Maximum operating frequency Operations/h 3000 Damp heat, constant, to IEC Climatic proofing 60068278 Damp heat, cyclical, to IEC 60068230 Ambient temperature Open C 25/50 Enclosed C 25/40 Mounting position As required Documentation Main catalogue HPL Mechanical shock resistance (shock g > 15 duration 20 ms) Contacts Rated operational voltage U V AC 690 e Rated impulse withstand voltage U V AC 6000 imp Overvoltage category/pollution III/3 degree Rated uninterrupted current open I A 100 u Enclosed I A 100 u Loadcarrying capacity in intermittent operation, Class 12 AB 25 % DF I 2 e AB 40 % DF I 1,6 e AB 60 % DF I 1,3 e Shortcircuit rating A Fuse 100 gG/gL Rated shorttime withstand current I A 1850 cw rms (1 s current) Safe isolation to VDE 0106 Part 101 and Part 101/A1 between the contacts V AC 440 90 60 Switching angles 45 30 Contact units 10 Doublebreak contacts max. 20 Current heat loss per contact at I W 7,5 e 2