Effective May 2017 Technical Data 2006 Supersedes October 2009 C515 5 mm x 15 mm Axial-leaded, time-delay, glass tube fuses Electrical Characteristics Rated Current Amp Rating Opening Time 135% 60 minutes max. 125mA - 250mA 3 seconds min. 200% 120 seconds max. 100% 4 hours min. 470mA 30 minutes max. 350mA 600mA 90 seconds max. 2A 2 seconds max. Product features 6A 500 milliseconds max. 135% 60 minutes max. Axial-leaded, time-delay 375mA - 7A 3 seconds min. 200% 120 seconds max. 5 x 15mm physical size Nickel-plated brass endcap construction Ordering Leads are tin coated Specify product code Optional sleeve is flexible flouropolymer Insert packaging code prefix before (UL Flammability rating VW-1). part number. UL Listed product meets standard UL 248-14 E.g., BK (or TR2)/C515-2-R With TR2 packaging code, lead wire Agency information length is 20.3mm Specify option code, UL Listed Card: C515 125mA-250mA and if desired 375mA-3A (Guide JDYX, File E19180) For insulation sleeve, insert S after UL Recognized Card: C515 350mA, and 3.5A-7A part series. E.g., BK/C515S-2-R (Guide JDYX2, File E19180) CSA Certification Card: C515 125mA-250mA and 375mA-3A (Class 1422-01, 53787 Speci cations Voltage Interrupting Typical DC Cold Max Product Code Rating Rating (amps) Resistance* Typical Voltage 2 Vac 600Vac 250Vac 125Vac () Melting I t** Drop (mV)*** C515-125-R 250 - 35 10000 4.72 0.101 770 C515-250-R 250 - 35 10000 1.32 0.467 430 C515-350-R 250 25 35 10000 1.04 1.169 530 C515-375-R 250 - 35 10000 0.81 1.531 470 C515-500-R 250 - 35 10000 0.54 2.280 440 C515-600-R 250 - 35 10000 0.38 6.982 350 C515-750-R 250 - 35 10000 0.26 9.162 310 C515-800-R 250 - 35 10000 0.23 10.544 260 C515-1-R 250 - 35 10000 0.14 14.289 230 C515-1.25-R 250 - 100 10000 0.13 22.961 220 C515-1.5-R 250 - 100 10000 0.100 31.989 240 C515-1.6-R 250 - 100 10000 0.090 35.156 200 C515-2-R 250 - 100 10000 0.059 60.256 170 C515-2.25-R 250 - 100 10000 0.057 97.724 180 C515-2.5-R 250 - 100 10000 0.046 78.163 190 C515-3-R 250 - 100 10000 0.035 80.426 150 C515-3.5-R 125 - - 400 0.028 149.279 130 C515-4-R 125 - - 400 0.023 233.346 130 C515-5-R 125 - - 400 0.019 354.813 150 C515-6-R 125 - - 400 0.014 471.360 125 C515-7-R 125 - - 400 0.013 710.500 100 *DC Cold Resistance (Measured at <10% of rated current) 2 2 2 **Typical Melting I t (A Sec) (Minimum I t at 10 times rated current) ***Typical Voltage Drop (Voltage drop was measured at 25C ambient temperature at rated current)C515 Technical Data 2006 Effective May 2017 5 mm x 15 mm Axial-leaded, time-delay, glass tube fuses Dimensions mm Drawing Not to Scale Time-Current Curves 10000 1000 100 10 1 0.1 0.01 0.1 1 10 100 Multiples of Rated Current Packaging Code Packaging Code Prefix Description BK 100 fuses packed into a cardboard carton TR2 1500 fuses packed into tape on a reel (20.3mm lead wire length) Option Code Option Code Description S Insulation Sleeve Life Support Policy: Eaton does not authorize the use of any of its products for use in life support devices or systems without the express written approval of an officer of the Company. Life support systems are devices which support or sustain life, and whose failure to perform, when properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in significant injury to the user. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Eaton Electronics Division 1000 Eaton Boulevard Cleveland, OH 44122 United States www.eaton.com/electronics 2017 Eaton Eaton is a registered trademark. All Rights Reserved Printed in USA All other trademarks are property Publication No. 2006 BU-SB09716 of their respective owners. May 2017 Pre-arcing time (s) 125mA 250mA 350mA 375mA 500mA 600mA 750mA 800mA 1A 1.25A 1.5A 1.6A 2A 2.25A 2.5A 3A 3.5A 4A 5A 6A 7A