Type: ZB322,4 Article No.: 278448 Ordering information Overload release, min. max. I A 1,6 2,4 r Auxiliary contacts M = Make 1 M Auxiliary contacts B = Break 1 B DILM17, DILM25, DILM32, DIULM17, DIULM25, For use with DIULM32, SDAINLM30, SDAINLM45, SDAINLM55 Shortcircuit protection Type 1 coordination gG/gL A 25 Shortcircuit protection Type 2 coordination gG/gL A 10 Contact sequence Note concerning the product Overload release: tripping class 10 A Shortcircuit protection: Observe the maximum permissible fuse of the contactor with direct device mounting. Suitable for protection of EEx emotors. EC prototype test certification on request. 1Notes concerning the product group Fitted directly to the contactorSeparate mounting 1 Contactor 051608 2 Bases 278473 General Standards IEC/EN 60947, VDE 0660, UL, CSA Damp heat, constant, to IEC 60068278 Climatic proofing Damp heat, cyclic, to IEC 60068230 Ambient temperature Open C 25/50 Enclosed C 25/40 Temperature compensation Continuous Weight Mechanical shock resistance halfsinusoidal shock 10 g 10 ms to IEC 60068227 Protection type IP00 Protection against direct contact when actuated from Finger and backofhand proof front (IEC 536) Main conducting paths Rated impulse withstand voltage U V AC 6000 imp Overvoltage category/pollution degree III/3 Rated insulation voltage AC U V AC 690 i Rated operational voltage U V AC 690 e Safe isolation to VDE 0106 Part 101 and Part 101/A1 Between auxiliary contacts and main contacts V AC 440 Between main circuits V AC 440 Overload release setting range A 0,1 32 Temperature compensation residual error > 20C %/K f 0.25 Current heat loss (3 conductors) Lower value of the setting range W 2,5 Maximum setting W 6 2